Download Print this page

Transport; Installation; General; Sound Emissions - Dimplex WI 140TUR+ Installation And Operating Instruction

Water-to-water heat pump for indoor installation

Advertisement

English
5

Transport

For the transport by means of a hand truck or boiler trolley, po-
sition the latter under the front end of the unit below the trans-
port security device.
For transport on a level surface, the unit can be lifted from the
rear or from the front by means of a lift truck or forklift. In this
case, the transport securing device is not imperative.
45°
ATTENTION!
The heat pump must not be tilted more than max. 45° (in
either direction).
After the transport, the transport securing device is to be re-
moved on either side at the bottom of the unit.
ATTENTION!
The transport securing device is to be removed prior to
commissioning.
To remove the panelling, open the individual covers by un-
screwing the respective turn-lock fasteners and then gently tilt-
ing the covers away from the device. Then lift them up out of
the mountings.
EN-6
45°
Remove/screw in
transport lock
452234.66.76 · FD 9912
6

Installation

6.1 General

The water-to-water heat pump must be installed in a frost-free,
dry room on an even, smooth and horizontal surface. The entire
frame should lie directly on the floor to ensure an adequate
soundproof seal. Failing this, additional sound insulation meas-
ures may become necessary.
The heat pump should be installed to allow easy maintenance/
service access. This is ensured if a clearance of approx. 1 m in
front of the heat pump is maintained.
Neither frost nor temperatures higher than 25°C must occur in
the installation location at any time of the year.

6.2 Sound Emissions

The heat pump offers silent operation due to efficient sound in-
sulation. Any vibration transmission to the foundation or the
heating system can be largely prevented by internal sound de-
coupling measures.
7

Assembly

7.1 General
The following connections need to be established on the heat
pump:
Flow and return of the well system
Flow / return of additional heat exchanger.
Flow and return of the heating system
Voltage supply
Temperature sensor
WI 140TUR+
0,5m
1m
www.gdts.one

Advertisement