Transport - Dimplex LA 1422C Installation And Operating Instruction

Air-to-water heat pump for outdoor installation
Table of Contents

Advertisement

English
4

Transport

CAUTION!
Risk of injury when lifting and setting down the load. Risk of
crushing!
Do not stand under the load when lifting and setting
down.
CAUTION!
Risk of injury if unsuitable lifting devices are used incorrectly.
Risk of falling and crushing!
People may only stand outside the danger area.
Observe the load capacity of the lifting devices and slings
used. (Germany: DGUV regulation 109-017)
CAUTION!
Risk of the heat pump tipping over if unsuitable attachment
points are used. Risk of falling and crushing!
The heat pump may only be lifted from the operator side
with a lift truck or forklift.
CAUTION!
Refrigerant may leak if the heat pump falls or is subject to
impact load during transport.
The unit must be checked immediately for leakages if it
falls or is subject to impact load during transport.
If outflow noises can be heard, if oily surfaces form or if a
leakage is detected with a detector, the refrigerant must
be drained off by a trained individual.
If the leakage occurs inside a building, the affected area
must be ventilated immediately.
The heat pump must be returned to the manufacturer for
repair if it is not possible to remedy the leakage onsite.
CAUTION!
The heat pump must not be tipped during transport. The
machine must be secured to prevent the risk of tipping.
A pallet should be used for transportation to the final installa-
tion location. The basic unit can be transported with a lift truck,
hand truck or by means of 3/4" pipes fed through the holes in
the baseplate or frame (max. pipe diameter in the evaporator-
compressor frame area, 25 mm). In the frame area, the pipes
must run parallel to the operator side (see figure).
Before using the transport holes in the frame, it is necessary to
remove the two bottom side panel assemblies. Each covering
panel is secured with two screws. Once the screws have been
loosened, the covering panels can be tilted (top plates by ap-
prox. 20°, bottom plates by approx. 45°). The bottom facade
EN-6
plates can then be pulled out of the skirt panel, the top facade
plates, which do not have to be removed for transport, can be
hung out of the cover plate. Rehang the top panels by gently
pushing them in an upwards direction.
NOTE
Be careful not to damage any components when inserting the
pipes through the frame.
The dust caps that were removed for usage of the transport
bores in the base must be re-inserted in order to prevent small
animals from entering into the interior of the unit and to ensure
sufficient sound insulation.
Once the heat pump has been set up in its intended location,
the transport fastenings (2x M6 screws) must be removed from
the compressor plate (the front or rear covering panel at the
bottom must be removed for this).
CAUTION!
Before commissioning, the transport fastening must be
removed.
452170.66.02-EN · FD 0305
LA 1422C
Remove/screw in
transport lock
www.dimplex.de