Protective Devices - Carrier 48HC D17 Series Service And Maintenance Instructions

Nominal 15 to 25 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

CONTROL OR INDICATOR
Magnetic test/reset switch
Alarm LED
Trouble LED
Dirty LED
Power LED
Resetting Alarm and Trouble Condition Trips:
Manual reset is required to restore smoke detector systems
to Normal operation. For installations using two sensors,
the duct smoke detector does not differentiate which
sensor signals an alarm or trouble condition. Check each
sensor's LED for Alarm or Trouble status. Clear the
condition that has generated the trip at this sensor. Then
reset the sensor by pressing and holding the reset button
(on the side) for 2 seconds. Verify that the sensor's Alarm
and Trouble LEDs are now off. At the controller, clear its
Alarm or Trouble state by pressing and holding the
manual reset button (on the front cover) for 2 seconds.
Verify that the controller's Alarm and Trouble LEDs are
now off. Replace all panels.
Troubleshooting
Controller's Trouble LED is On
1. Check the Trouble LED on each sensor connected to
the controller. If a sensor's Trouble LED is on, de-
termine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
Controller's Trouble LED is Flashing
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean
that sensor assembly as described in the detector
cleaning section.
Sensor's Trouble LED is On
1. Check the sensor's Dirty LED. If it is flashing, the
sensor is dirty and must be cleaned.
2. Check the sensor's cover. If it is loose or missing, se-
cure the cover to the sensor housing.
3. Replace sensor assembly.
Sensor's Power LED is Off
1. Check the controller's Power LED. If it is off, de-
termine why the controller does not have power and
make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
Controller's Power LED is Off
1. Make sure the circuit supplying power to the
controller is operational. If not, ensure JP2 and JP3
are set correctly on the controller before applying
power.
2. Verify that power is applied to the controller's supply
input terminals. If power is not present, replace or re-
pair wiring as required.
Table 5 – Detector Indicators
Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in
the normal state.
Indicates the sensor is in the alarm state.
Indicates the sensor is in the trouble state.
Indicates the amount of environmental compensation used by the sensor
(flashing continuously = 100%)
Indicates the sensor is energized.
37
DESCRIPTION
Remote Test/Reset Station's Trouble LED Does Not
Flash When Performing a Dirty Test, But the
Controller's Trouble LED Does
1. Verify that the remote test/station is wired as shown
in Fig. 43. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the control-
ler's supervision relay. See "Changing sensor dirty
test operation."
Sensor's Trouble LED is On, But the Controller's
Trouble LED is OFF
Remove JP1 on the controller.

PROTECTIVE DEVICES

Compressor Protection
Overcurrent
Each compressor has internal linebreak motor protection.
Reset is automatic after compressor motor has cooled.
Overtemperature
Each compressor has an internal protector to protect it
against excessively high discharge gas temperatures. Reset
is automatic.
High Pressure Switch
Each system is provided with a high pressure switch
mounted
on
the
discharge
stem- - mounted and brazed into the discharge tube. Trip
setting is 630 psig
10 psig (4344
Reset is automatic at 505 psig (3482 kPa).
Low Pressure Switch
Each system is protected against a loss of charge and low
evaporator coil loading condition by a low pressure switch
located on the suction line near the compressor. The
switch is stem- - mounted. Trip setting is 54 psig
(372
34 kPa). Reset is automatic at 117
34 kPa).
line.
The
switch
is
69 kPa) when hot.
5 psig
5 psig (807