Start- - Up, Rtu- - Open Control; Fastener Torque Values - Carrier 48HC D17 Series Service And Maintenance Instructions

Nominal 15 to 25 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

START- -UP, RTU- - OPEN CONTROLS
NOTICE
SET- - UP INSTRUCTIONS
Refer to the following manuals for additional
installation, wiring and troubleshooting information
for the RTU- - OPEN Controller.: "Controls, Start- - up,
Operation and Troubleshooting Instructions," "RTU
Open
Installation
and
"RTU- - Open Integration Guide". Have a copy of these
manuals available at unit start- - up.
Table 20 – Torque Values
Supply fan motor mounting
Supply fan motor adjustment plate
Motor pulley setscrew
Fan pulley setscrew
Blower wheel hub setscrew
Bearing locking collar setscrew
Compressor mounting bolts
Condenser fan motor mounting bolts
Condenser fan hub setscrew
Start- - up
Guide"
and
FASTNER TORQUE VALUES
120 in--- lbs (13.6 Nm)
120 in--- lbs (13.6 Nm)
72 in--- lbs (8.1 Nm)
72 in--- lbs (8.1 Nm)
72 in--- lbs (8.1 Nm)
50 in--- lbs (6.2 Nm) --- 60 in--- lbs (6.8 Nm)
65 in--- lbs (7.3 Nm) --- 75 in--- lbs (8.5Nm)
20 in--- lbs (2.3 Nm)
84 in--- lbs (9.5 Nm)
12 in--- lbs (1.4Nm)
12 in--- lbs (1.4Nm)
5 in--- lbs (0.6 Nm)
5 in--- lbs (0.6 Nm)
5 in--- lbs (0.6 Nm)
2 in--- lbs 0.2 Nm)
12 in--- lbs (1.4 Nm)
65