Convenience Outlets - Carrier 48HC D17 Series Service And Maintenance Instructions

Nominal 15 to 25 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

CONVENIENCE OUTLETS

WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits can use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
the disconnect switch, and disconnect all electrical
power to the switch. Use appropriate Lockout/Tag- - out
procedures as needed.
Two types of convenience outlets are offered on 48HC
models: Non- - powered and unit- - powered. Both types
provide a 125-volt Ground- - Fault Circuit- - Interrupter
(GFCI) duplex receptacle rated at 15-A behind a hinged
waterproof access cover, located on the end panel of the
unit. See Fig. 34.
Non- -Powered Type
This
type
requires
the
general- - purpose 125- - volt 15- - A circuit powered from a
source elsewhere in the building. Observe national and
local codes when selecting wire size, fuse or breaker
requirements and disconnect switch size and location.
Route 125- - v power supply conductors into the bottom of
the utility box containing the duplex receptacle.
CONVENIENCE
OUTLET GFCI
Fig. 34 - - Convenience Outlet Location
Unit- -Powered Type
A unit- - mounted transformer is factory- - installed to
stepdown the main power supply voltage to the unit to
115VAC at the duplex receptacle. This option also
includes a manual switch with fuse, located in a utility
box and mounted on a bracket behind the convenience
outlet; access is through the unit's control box access
panel. See Fig. 34.
field
installation
of
PWD-CO TRANSFORMER
PWD-CO FUSE
SWITCH
CONTROL BOX
ACCESS PANEL
C08128
a
UNIT
CONNECT
VOLTAGE
AS
208,
240
230
460
480
575
600
Fig. 35 - - Powered Convenience Outlet Wiring
Wet in Use Convenience Outlet Cover
The unit has a "wet in use" convenience outlet cover that
must be installed on panel containing the convenience
outlet. This cover provides protection against moisture
entering the GFCI receptacle. This cover is placed in the
unit control box during shipment.
Duty Cycle
The unit- - powered convenience outlet has a duty cycle
limitation. The transformer is intended to provide power
on an intermittent basis for service tools, lamps, etc. It is
not intended to provide 15- - amps loading for continuous
duty loads (such as electric heaters for overnight use).
Observe a 50% limit on circuit loading above 8- - amps
(i.e., limit loads exceeding 8- - amps to 30 minutes of
operation every hour).
29
PRIMARY
TRANSFORMER
CONNECTIONS
TERMINALS
L1: RED +YEL
H1 + H3
L2: BLU + GRA
H2 + H4
L1: RED
H1
Splice BLU + YEL
H2 + H3
L2: GRA
H4
L1: RED
H1
L2: GRA
H2
C10324