Carrier 48HC D17 Series Service And Maintenance Instructions page 50

Nominal 15 to 25 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

NATURAL GAS
ELEVATION
Feet
0 --- 2000
2000
3000
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
PROPANE GAS
ELEVATION
Feet
0 --- 2000
2000
3000
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
* As the height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, heat input rate should be reduced at higher altitudes.
KIT NO.:
1
XX
= CRNGELEV001A00
2
XX
= CRNGELEV002A00
3
XX
= CRLPELEV005A00
4
XX
= CRLPELEV006A00
5
XX
= CRLPKIT9001A00
Minimum Heating Entering Air Temperature
When operating on first stage heating, the minimum
temperature of air entering the dimpled heat exchanger is
50_F (10_C) continuous and 45_F (7_C) intermittent for
standard heat exchangers and 40_F (4_C) continuous and
35_F
(2_C)
intermittent
exchangers. To operate at lower return or mixed air
temperatures, a field- - supplied outdoor- - air thermostat
must be used to initiate both stages of heat when the
temperature is below the minimum required temperature
to ensure full fire operation. Wire the outdoor- - air
thermostat (OALT) (part no. HH22AG106) in series with
the second stage gas valve. See Fig. 62. Set the
outdoor- - air thermostat at 35_F (2_C) for stainless steel
heat exchangers or 45_F (7_C) for standard heat
Table 14 - - Altitude Compensation* (17 - - 30) - - Natural Gas
220k BTUH
Orifice
Input
Meters
Size
(btu/hr)
0 --- 610
30
220,000
610
30
202,400
1
914
31
193,600
1
1219
31
184,800
1
1524
31
176,000
1
1829
31
167,200
1
2134
32
158,400
1
2438
32
149,600
1
2743
34
140,800
2
3048
35
132,000
2
3353
37
123,200
2
3658
37
114,400
2
3962
39
105,600
2
4267
39
96,800
Table 15 – Altitude Compensation* (17 - - 30) - - Propane Gas
220k BTUH
Orifice
Input
Meters
Size
(btu/hr)
5
0 --- 610
48
220,000
3
610
49
202,400
3
914
49
193,600
3
1219
49
184,800
3
1524
50
176,000
3
1829
50
167,200
3
2134
50
158,400
3
2438
51
149,600
3
2743
51
140,800
4
3048
52
132,000
4
3353
52
123,200
4
3658
53
114,400
4
3962
53
105,600
4
4267
53
96,800
for
stainless
steel
heat
NOMINAL HEAT INPUT
310k BTUH
400k BTUH
Orifice
Input
Orifice
Size
(btu/hr)
Size
30
310,000
30
30
285,200
30
1
1
31
272,800
31
1
1
31
260,400
31
1
1
31
248,000
31
1
1
31
235,600
31
1
1
32
223,200
32
1
1
32
210,800
32
1
1
34
198,400
34
2
2
35
186,000
35
2
2
37
173,600
37
2
2
37
161,200
37
2
2
39
148,800
39
2
2
39
136,400
39
NOMINAL HEAT INPUT
310k BTUH
400k BTUH
Orifice
Input
Orifice
Size
(btu/hr)
Size
5
5
48
310,000
48
3
3
49
285,200
49
3
3
49
272,800
49
3
3
49
260,400
49
3
3
50
248,000
50
3
3
50
235,600
50
3
3
50
223,200
50
3
3
51
210,800
51
3
3
51
198,400
51
4
4
52
186,000
52
4
4
52
173,600
52
4
4
53
161,200
53
4
4
53
148,800
53
4
4
53
136,400
53
exchangers. This temperature setting will bring on the
second stage of heat whenever the ambient temperature is
below the thermostat setpoint. Indoor comfort can be
compromised when heating is initiated using low entering
air temperatures with insufficient heating temperature rise.
Thermostat
TH1
W1
TH2
W2
50
Input
(btu/hr)
400,000
368,000
352,000
336,000
320,000
304,000
288,000
272,000
256,000
240,000
224,000
208,000
192,000
176,000
Input
(btu/hr)
400,000
368,000
352,000
336,000
320,000
304,000
288,000
272,000
256,000
240,000
224,000
208,000
192,000
176,000
LCTB
W1
OALT
W2
C08442