Point Name
Humidistat/LTLO
Thermostat W1
Econ Y1
Thermostat G
24V Power (J1)
24V Power (J2)
Econ Y2
COMP1
IFM
COMP2
LSV
DSV1
NOT LSV
DSV2
LEGEND
COMP ---
Compressor
CTB
. .
---
Control Terminal Board
DI
. . .
---
Discrete Input (switch)
DO
. . .
---
Discrete Output (switch)
DSV
. .
---
Discharge (gas) Solenoid Valve
Econ
.
---
Economizer
FPT
. .
---
Freeze Protection Thermostat
IFM
. .
---
Indoor (Supply) Fan motor
LSV
. .
---
Liquid Solenoid Valve
LTLO
.
---
Low Temperature Lockout
REHEAT
. .
---Connection Strip REHEAT (on CTB)
Y1
Y2
W1
G
HUM/
LTLO
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
On
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
X
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
X
ON
OFF
OFF
ON+
X
ON
W2
Fig. 19 - - Humidi- - MiZer Reheat Control Board I/O
Type
Connection
Pin Number
DI, 24VAC
J1A ---1 (1)
DI, 24VAC
J1A ---2 (2)
DI, 24VAC
J1A ---6 (6)
DI, 24VAC
J1B---1 (7)
24VAC
J1B---3 (9)
24 VAC
J2---1
DI, 24VAC
J1B---5 (11)
DO, 24VAC
J1A ---5 (5)
DO, 24VAC
J1B---4 (8)
DO, 24VAC
J1B---4 (10)
DO, 24VAC
J2---2
DO, 24VAC
J2---3
DO, 24VAC
J2---4
DO, 24VAC
J2---5
Fig. 20 - - Inputs/Modes/Outputs Summary
MODE
COMP1
Normal
Fan
OFF
Normal
Cool1
ON=Y1
Normal
Cool2
0N=Y2
Normal
Heat 1
OFF
Reheat
Dehumidify
Subcool
Cool1 and
Cir1/
Cool2/Subcool---
Reheat
Dehumidify
Cir2
Subcool
Cool1 and
Cir1 and
Cool2/Subcool---
Cir2
Dehumidify
Heat Over-
Heat 1
OFF
ride
Heat Over-
Heat 1 and 2
OFF
ride
Unit
Connection
LTLO
CTB---REHEAT---4
CTB---REHEAT---5
CTB---REHEAT---1
CTB---R
CTB---R
CTB---REHEAT---7
CTB---HEAT ---6
CTB---REHEAT---2
CTB---REHEAT---8
FTP (BLK)
DSV
COMP2
IFM
LSV1
OFF
ON=G
OFF
OFF
ON=G
OFF
ON
ON=G
OFF
OFF
ON=G
OFF
ON
ON
ON=G
ON
ON
ON
ON=G
ON
ON
ON
ON=G
ON
OFF
ON=G
OFF
OFF
ON=G
OFF
16
Note
2---circ only
2---circ only
2---circ only
LSV2
LSV
DSV1
DSV2
NOT
OFF
ON=R
OFF
OFF
OFF
ON=R
OFF
OFF
OFF
ON=R
OFF
OFF
OFF
ON=R
OFF
OFF
ON
OFF
ON=R
ON=R
ON
OFF
OFF
ON=R
ON
OFF
OFF
OFF
OFF
ON=R
OFF
OFF
OFF
ON=R
OFF
OFF