The PremierLink controller (see Fig. 46) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory- - defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilott, Touch Pilott and
Service Tool. Standard tier display tools, Navigatort and
Scrolling Marquee, are not suitable for use with the latest
PremierLink controller (Version 2.x).
PREMIERLINK
Fig. 46 - - PremierLink Controller
The PremierLink control is factory- - mounted in the 48HC
unit's main control box to the left of the LCTB. Factory
wiring is completed through harnesses connected to the
LCTB thermostat. Field connections are made at a
16- - pole terminal block (TB1) located on the bottom shelf
of the unit control box in front of the PremierLink
controller The factory- - installed PremierLink control
includes the supply- - air temperature (SAT) sensor. The
outdoor air temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er 2 package.