All Units; Convenience Outlets - Carrier WeatherMaster 50HCQ 04 Series Installation Instructions Manual

Single package rooftop heat pump with puron (r-410a) refrigerant
Table of Contents

Advertisement

Units Without Disconnect Option
C
C
11
23
11
Disconnect
Disconnect
per
NEC
L1
208/230-1-60
208/230-3-60
460-3-60
575-3-60
Units With Disconnect Option
L1
2
Disconnect
L2
4
L3
6
Disconnect factory test leads; discard.
Fig. 23 — Power Wiring Connections

ALL UNITS

All field wiring must comply with NEC and all local codes. Size
wire based on MCA (Minimum Circuit Amps) on the unit infor-
mative plate. See Fig. 23 and the unit label diagram for power wir-
ing connections to the unit power terminal blocks and equipment
ground. Maximum wire size is #2ga AWG (copper only) per pole.
Provide a ground fault and short circuit over-current protection de-
vice (fuse or breaker) per NEC Article 440 (or local codes). Refer
to unit informative data plate for MOCP (Maximum Over-Current
Protection) device size.
NOTE: All field wiring must comply with the NEC and local
requirements.
All units except 208/230v units are factory wired for the voltage
shown on the nameplate. If the 208/230v unit is to be connected to
a 208v power supply, the control transformer must be rewired by
removing the black wire with the
from the 230v connection and moving it to the 200v
terminal on the primary side of the transformer. Refer to unit label
diagram for additional information. Field power wires will be
connected at line-side pressure lugs on the power terminal block
or at factory-installed option non-fused disconnect.
NOTE: Check all factory and field electrical connections for
tightness.

CONVENIENCE OUTLETS

WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or
death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status before
opening unit for service. Locate its disconnect switch, if
appropriate, and open it. Lock-out and tag-out this switch, if
necessary.
IFC
(3 Phase
Indoor Motor)
(1 Phase Indoor Motor
13
13
TB
and 3 Phase Unit)
per
NEC
L2
L3
1
Optional
Factory
3
Wiring
Switch
5
1
/
-in. female spade connector
4
/
-in. male
1
4
Two types of convenience outlets are offered on 50HCQA mod-
els: non-powered and unit-powered. Both types provide a 125-volt
GFCI (ground-fault circuit interrupter) duplex receptacle rated at
15A behind a hinged waterproof access cover, located on the end
panel of the unit. See Fig. 24.
CONVENIENCE
OUTLET GFCI
Fig. 24 — Convenience Outlet Location
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory-installed conve-
nience outlets is now required by UL standards. This cover cannot
be factory-mounted due its depth; it must be installed at unit instal-
lation. For shipment, the convenience outlet is covered with a
blank cover plate.
The weatherproof cover kit is shipped in the unit's control box.
The kit includes the hinged cover, a backing plate, and gasket.
Failure to follow this caution could result in personal injury or
death.
Disconnect all power to unit and convenience outlet. Lock-out
and tag-out all power.
1.
Remove the blank cover plate at the convenience outlet; dis-
card the blank cover.
2.
Loosen the two screws at the GFCI duplex outlet, until
approximately
1/
in. (13 mm) under screw heads is exposed.
2
Press the gasket over the screw heads.
3.
Slip the backing plate over the screw heads at the keyhole
slots and align with the gasket; tighten the two screws until
snug (do not over-tighten).
4.
Mount the weatherproof cover to the backing plate as shown
in Fig. 25.
5.
Remove two slot fillers in the bottom of the cover to permit
service tool cords to exit the cover.
6.
Check for full closing and latching.
16
PWD-CO TRANSFORMER
PWD-CO FUSE
SWITCH
CONTROL BOX
ACCESS PANEL
WARNING