Fig. 8-3: Status Displays - Bosch Rexroth VAM 10.1 Project Planning Manual

Table of Contents

Advertisement

8-4
Commissioning
Pos
Light-emitting diode
H1
"UL"
H2
"DIA"
H3
"RUN"
H4
"BF"
Display
Meaning
24 V supply (connector X10)
24 V supply is available
Green
The bus connection is kept in the initialization phase by one or several
Green~
modules.
System stop (see table system stop)
Green~~
No 24 V supply available
Off
Diagnostic display
Red
One or several modules indicate a diagnosis.
System stop (see table system stop)
~
Red
System stop (see table system stop)
Red~~
No diagnosis or system stop
Off
Operating display
Green
Cyclic I/O data exchange (normal operation)
Configuration error (command/actual assignment is different)
Green~
The bus connection is not activated by the DP master.
Off
Causes:
Faulty PROFIBUS DP station address
The PROFIBUS DP station address is assigned several times at
the bus.
The response monitoring time is expired.
Error in master parameter set (GSD file); e. g. wrong PNO-ID
number, wrong buffer seize (Prm, Cfg, ...)
Incorrect parameterization in User_Prm_Data[1]
Bus error
Red
The bus connection is searching the baud rate.
Parameterization error (invalid parameterization data)
~
Red
The bus connection has recognized and applied the baud rate.
Off
L:
Green
Green~
Green~~ slow flashing of the display (0.125 s On / 0.125 s Off)
Fig. 8-3:
Status displays
static display
slow flashing of the display (0,8 s On / 0,2 s Off)
DOK-SUPPL*-VAM*10/40**-PR02-EN-P
VAM 10.1 / VAM 40.1