Omron CJ Series Operation Manual page 282

Master unit
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Appendices
Number
00
Total I/O area size exceeds
maximum
01
CPU Memory overlapping
02
CPU Memory exceeds mem-
ory range
03
Slaves should have unique
addresses
04
DTM cannot be added to the
network, it is not a PROFI-
BUS device DTM
05
Max. number of slaves con-
figured. New slave cannot be
added
06
Slave address overlap
detected. New address
assigned: [new address]
07
Invalid data set received from
a slave DTM. Slave parame-
ter changes ignored
08
Set Parameters failed. Slave
cannot be configured
09
No slaves assigned. Down-
load aborted
10
Slave(s) has no modules.
Download aborted
11
Configured EM bank (banks)
is not available in the con-
nected CPU.Download
aborted
12
Connected unit is busy.
Download aborted
13
Slave configuration too big
14
Maximum number of modules
exceeded
15
PROFIBUS Master is not in
correct mode. Please set the
PROFIBUS Master in one of
the following modes: STOP,
CLEAR or OPERATE.
A-16
Message
The I/O configuration exceeds the
maximum limit of 7168 (or 7k) words).
Input/Output areas and/or PROFIBUS
DP-V1 Status table are overlapping
within the current configuration.
Input/Output areas and/or PROFIBUS
DP-V1 Status table exceeds memory
range (combination of start address
and length).
Unique bus addresses must be
assigned for each slave.
The slave DTM cannot be connected,
e.g. if adding HART device DTM.
DTM can not be added, since the
master has already the maximum
number of slaves (125) assigned.
Changing the address of an existing
slave results in an address overlap.
An internal error has occurred pre-
venting the master DTM to obtain the
slave's parameter set.
An internal error has occurred pre-
venting the master DTM from set-
ting/changing the slave's bus
address.
No slaves have been assigned to the
master. At least one slave must be
assigned.
A slave (or slaves) has no modules.
The configured EM bank (banks) are
not available in the connected CPU.
Unit is busy with parameter storage.
The total number of configured
parameter bytes and configuration
bytes does not fit into the message for
downloading.
The total number of configured I/O
modules over all allocated slave
devices can not exceed 4000.
The Set Device Station Address com-
mand can not be executed because
the PROFIBUS Master is not in cor-
rect mode, i.e. the Master Unit is
OFFLINE.
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
Description
Change configuration to reduce the
amount of I/O data to 7168 words
maximum or less.
Check the Input/Output areas and
make sure they are not overlapping.
Retry download.
Change the configuration to be within
the memory area and retry download.
Change the addresses of the slaves
and ensure no duplicates are present.
Retry download.
Avoid using non-PROFIBUS DP
DTMs.
Do not add any more DTMs. If more
are still needed, a second PROFIBUS
Master Unit on the same CPU system
may be solution.
Automatically recovers.
Add a new slave DTM into the net-
work (or change the modules of the
existing slave) with correct slave
parameter set.
Non recoverable. Master DTM tries to
assign a new bus address to the
slave DTM, but the slave DTM's data-
base is locked.
Retry download when at least one
slave has been assigned.
Retry download when modules have
been added to the slave(s) having no
modules.
Change the configuration to use only
memory areas available in the CPU
and retry download.
Retry download when parameter stor-
age has finished.
Reduce the configuration.
Do not add any more modules to the
configuration.
Set the PROFIBUS Master into one of
the following modes: STOP, CLEAR
or OPERATE.
Correction