Group Tab
In the Group tab the user can define to which group the slave device will belong. This group defini-
tion is used to define multi-cast groups of slave device to which a Global-Control command can be
transmitted. The window is shown below.
 Selecting the Groups
The user can check the check boxes for each group the slave device will belong to. The group set-
ting is transferred to the slave device as part of the parameter message.
The three tabs discussed above, allow for making all the standard PROFIBUS DP settings for a
slave device. For slave devices supporting PROFIBUS DP-V1, two additional tabs will show up.
These tabs will appear, if the GSD file parameter GSD_Revision is set to 3 or higher. The additional
tabs are discussed below.
Extensions Tab
The Extensions tab contains a number of settings, which define additional behavior of the CJ1W-
PRM21 PROFIBUS Master Unit with respect to a particular PROFIBUS DP-V1 slave device.
Although this specific behavior is defined in the PROFIBUS DP extensions standard (PROFIBUS
DP-V1) it does not necessarily require PROFIBUS DP-V1 capabilities from the PROFIBUS Master
Units. The Extension tab is shown below.