Omron CJ Series Operation Manual page 257

Master unit
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Error
Meaning
Code
0211
Duplicate master address
0219
Hardware error
021A
Logic error in setting table 00
0601
CPU Bus Unit fatal error
0602
CPU Bus Unit memory
error
Note 1 The time information from the CPU Unit is used in the PROFIBUS Master Unit.
2 An error record is not created in non-volatile memory when the error concerns an Error Log
Write error.
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
Detailed Codes
First byte
Second byte
00
00 to 7D: Failing
Master Address
00
00
03: Routing
tables
Error address in program.
01: Read error.
02: Network
Parameter.
02: Write error.
06: Error log.
7 Troubleshooting and Maintenance
Correction
Check the master devices on the
network and ensure that they have
unique device addresses.
• Check the network wiring, and
make sure it is correct.
• Check for short-circuits.
• Check the bus timing set through
CX-ConfiguratorFDT.
• Check the HSA setting in CX-
ConfiguratorFDT and make sure it
is set to the master device with
the highest address on the net-
work.
• Check if any other faulty devices
are on the same network.
• Verify that the Highest Station
Address setting includes any
other master address on the bus.
Recreate the data specified by the
2nd byte of the detailed error code.
Restart the CPU Unit. If the problem
persists, replace the PROFIBUS
Master Unit.
Restart the CPU Unit. If the problem
persists, replace the PROFIBUS
Master Unit.
Non-vol-
atile
Saved
Saved
Saved
7
7-25