J7 and J1000 Differences in Parameter Settings

Maximum carrier frequency
-
J7: n46, max. 10 kHz
J1000: C6-02, max. 15 kHz
S-Curve setting
-
J7: fixed settings
J1000: set in seconds
Stall Prevention Level
-
The stall prevention level during acceleration and constant speed run depends on the duty
mode setting.
J7:
J1000:
J7
Parameter
Initial Value
No.
0
H5-01
2
H5-02
0
H5-03
10ms
H5-06
0
H5-07
0
L8-38
rdy
o3-01
0
o3-02
-
U2-01/02
-
U1-25/26
The maximum setting of n56/57 is 200%
Heavy Duty, The maximum setting of L3-02 and L3-06 is 150%
Normal Duty, The maximum setting of L3-02 and L3-06 is 120%
VAN-V07007E  [J7→J1000] Replacement Instructions
J1000
Initial Value
J7: set as decimal value
1F
J1000: set as hexadecimal value
J7
n71→0
n71→1
3
n71→2
n71→3
J7
n72→0
0
n72→1
n72→2
10 ms
J7
n74→0
1
n74→1
J7
depends on
n75→0
drive
n75→1
capacity
Possible
0
operator.
In the J1000 the last current fault and the
0
last fault can be seen in parameter U2-01
and U2-02
-
-
Comments
J1000
H5-02→1
H5-02→2
H5-02→3
H5-02→4
J1000
H5-03→1
H5-03→2
H5-03→0
J1000
H5-07→1
H5-07→0
J1000
L8-38→0