Start-up

Following the completion of all check list items, start up the unit for a test run.
CAUTION! To conduct a run test that involves the measurement of motor and fan performances, the unit must be
connected to the complete installation.
Sound power levels
CAUTION! All access doors must be closed to avoid overflow in the installation that could result in motor damage
and to avoid safety risks to people.
Discharge
CAUTION! Before starting the fan, open all dampers. The fan must not be started if the dampers are closed.
After switching on power, check that the direction of the fan rotation is correct. In addition, the running power
Measurement conditions:
consumption should be checked on all phases and compared with the power data indicated on the motor nameplate.
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
If the running power is too high, there is probably a faulty connection and the unit must be switched off immediately.
long) fixed to its discharge opening.
Check the fan and motor bearings for undue noise.
Fan
Measure the air volume and external pressure.
Unit
speed
The following two situations may arise:
1

FWD 08

2
1.
The air volume is too low as the real external static pressure is higher than the specified one.
3
1
Recommended action: increase the air volume by changing or adjusting the belt drive pulleys.
FWD 10
2
Please contact your local Trane sales office to get a proper belt drive selection.
3
1
CAUTION! Do not increase the fan speed beyond the motor power rating allowed limit.
FWD 12
2
CAUTION! Increasing the fan speed should be done only after a careful study of the operating point on the
3
1
appropriate fan curve.
FWD 14
2
Contact your local Trane sales office for a proper selection.
3
1
2.
The air volume is too high. The reason is that the real external static pressure is lower than the specified one.
FWD 20
2
3
Result: Higher air volume involves a high motor absorbed power increase.
CAUTION! Motor overload may result in motor damage.
Intake
Recommended action: change the belt drive pulleys or reduce the fan rpm according to the fan curve or reduce the
air volume by the use of dampers.
Measurement conditions:
Measurements taken at the horizontal air intake.
Ask a proper transmission selection from your local sales office.
In extreme cases, changing the motor, fan, and drive may be necessary.
Fan
The adjustment of variable belt drive pulleys must be carried out only when the unit is electrically disconnected,
Unit
speed
1
ensuring that the system is not restarted unexpectedly.
FWD 08
2
Remove the pulley safety screws and turn through half of the pulley circumference. Then retighten the screws and
3
readjust the pulley belt tension (see Figure 21.)
1
FWD 10
2
Following any change in the pulley ratio, the motor power consumption must be rechecked. The nominal output
3
rating quoted on the name plate must not be exceeded.
1
FWD 12
2
If airflow does not conform to the specifications, please contact your local Trane sales office.
3
1
Note: The unit structure is designed so that it will not suffer permanent deformation up to a positive pressure
FWD 14
2
or negative pressure of 2000 Pa. To respect these limits, fan operation should be controlled depending on all
3
interception devices installed in the plant and/or in the air handling unit.
1
FWD 20
2
3

Evaporative Humidifiers/air washers

Water tanks must be thoroughly cleaned. Any building grit in the system may result in subsequent pump failure. Any
warranty claims in this context will not be accepted. Check that the pump suction filter basket, spray pipes, washer
nozzles are correctly seated. Check the washer sieve and clean as necessary.
Fill the tank and siphon with clean water and adjust the float valve so that closure occurs 2-3 cm below the overflow
level. In any case the suction pipe must be effectively vented. Then check that the pump rotation direction is correct.
Measure the absorbed power and check that it matches the data indicated on the pump name plate.
CAUTION! : The pump must not be dry run to avoid any risk of overheating.
No warranty claims will be acknowledged if pump or pump motor damage is caused by a dry run.
AH-SVX03C-GB
UNT-PRC002-GB
Power level in dB(A), per Hz frequency band
125
250
500
55
50
42
57
54
47
58
57
50
57
51
45
58
54
48
60
58
50
57
51
45
58
54
48
60
58
50
56
62
50
61
66
55
63
69
58
57
63
51
61
66
55
63
69
58
Power level in dB(A), per Hz frequency band
125
250
500
56
55
55
63
62
60
66
65
63
62
58
55
66
63
60
70
67
63
62
58
55
66
63
60
70
67
63
66
65
65
73
72
69
78
76
73
68
72
64
76
76
68
78
79
71
Commissioning procedure
1000
2000
4000
37
37
31
40
30
38
42
32
40
42
34
33
45
38
39
48
40
42
42
34
33
45
38
39
48
40
42
48
39
38
53
47
46
56
50
50
49
40
39
53
47
46
56
50
50
1000
2000
4000
53
46
45
60
53
53
62
56
55
58
51
48
62
56
55
65
59
59
58
51
48
62
56
55
65
59
59
65
57
50
71
64
59
75
69
64
64
56
52
71
65
61
74
69
66
Overall power
8000
dB(A)
30
46
40
50
43
53
28
48
35
51
39
54
28
48
35
51
39
54
36
56
45
60
49
63
37
57
45
60
49
63
Overall power
8000
dB(A)
42
57
53
64
57
67
44
61
52
66
57
69
44
61
52
66
57
69
46
68
57
74
63
78
50
69
61
75
66
78
11
25