Commissioning procedure
Filters
The filter cells or media (bag filters, heap filters, and roll filters) delivered separately must be installed into the unit
prior starting the unit.
Check that the filter is correctly fitted and that the entering air side of the filter is exposed to the contaminated air
stream. Refer to the certified submittals which maybe different.
FWD
Power supply
If roll filters are used, check that the filter unit drive motor and the switch control are working correctly.
Capacities
Cooling capacity on water (1)
Humidifiers
Heating capacity on water (2)
The evaporative humidifiers with or without recirculating pump are provided with a water flow control valve.
Fan motor
Fan power input (3)
During fan operation, with the door closed, adjust the water flow control valve to prevent water leakage from the
Current amps (3)
pump hydroscopic plastic honeycomb humidifier.
Start-up amps
Air flow
The following safety procedures are strongly recommended:
minimum
nominal
• Connect the power supply to the pump.
maximum
• Check that pump rotation is correct.
Main coil
• Check that access doors of all sections, but the one being used, are closed. The door of the section in use should be
Water entering/leaving connections
kept in open position with a shim.
Electric heater (accessory for blower only)
• Slightly open the water flow control valve towards the humidifier.
Electric power supply
• If the humidifier is with honeycomb, ensure there is no water leakage from the honeycomb humidifier. If you
Heating capacity
notice leakage, close the valve and check again. If it is operating correctly, open the control valve until the system
Hot water coil (accessory for blower only)
Heating capacity (4)
reaches its best balance.
G2 filter (filter box accessory)
• If the humidifier is with nozzles, check that water is not coming out from the limit of humidification section and do
Quantity
not spray on the casing.
Dimensions ( LxWxth)
• Measure the absorbed power and check that it matches the data indicated on the pump name plate.
G4 filter (filter box accessory)
Quantity
CAUTION! The above mentioned operations should be performed from outside of the unit. Do not enter the sections.
Dimensions ( LxWxth)
Condensate pump (accessory)
CAUTION! The pump must not be dry run to avoid any risk of overheating.
Water flow - lift height
No warranty claims will be acknowledged if pump or pump motor damage is caused by a dry run.
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Note: If installation and start-up do not occur immediately after delivery, take the following precautions:
Sound pressure level (5)
• Store the equipment in an area that is not exposed to excessive humidity.
Sound power level (5)
• Take special care to protect electrical components.
Unit dimensions
Width x Depth
• Periodically, manually turn all moving parts to avoid any blocking risks.
Height
CAUTION! for other type of humidifier (steam, compressed water, water and compressed air, others), refer to
Shipped unit dimensions
Width x Depth
Manufacturer instruction and IOM.
Height
Water quality for humidifiers and air washers
Weight
Colour
The information hereunder which refers to the water treatment is given for reference only. Water quality is of prime
Recommended fuse size
concern to ensure proper operation of humidifier and air washer.
Unit alone (aM/gI)
Unit with electric heater (gI)
The water hardness of the freshwater has to be measured before considering any water treatment.
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
CAUTION! The use of improperly treated or untreated water in this equipment may result in scaling, erosion,
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
treatment, if any, is required.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
The Trane warranty specifically excludes liability for corrosion or deterioration.
Heat exchanger operating limits:
Trane assumes no responsibility for equipment damage or failure which results from the use of untreated or
FWD:
*water temperature: max 100° C
improperly treated water or saline or brackish water.
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
4
24
Technical Data
08
(V/Ph/Hz)
(kW)
5,2
(kW)
6,3
(type)
(kW)
0,23
(A)
1,1
(A)
3,2
(m
/h)
490
3
(m
/h)
820
3
(m
/h)
980
3
(type)
(Dia)
3/4"
(V/Ph/Hz)
230/1/50
(kW)
2/4
(kW)
6,3
2
(mm)
386x221x8
-
(mm)
-
(type)
(l/h - mm)
(dB(A))
36/40/43
(dB(A))
46/50/53
(mm)
890 x 600
(mm)
250
(mm)
933 x 644
(mm)
260
(kg)
32
(A)
8/16
(A)
16 (2kW),25 (4kW)
12
20
230/1/50
8,3
15
11,9
18,9
2 x direct drive centrifugal
0,46
0,65
2,2
3,1
5,5
9,3
980
1400
1650
2300
1970
2600
ISO R7 rotating female
3/4"
1 1/2"
230/1/50 or 400/3/50
400/3/50
8
10
12
17,4
2
2
486x271x8
586x321x8
2
2
486x264x48
586x314x48
Centrifugal
24 - 500
38/41/44
46/50/53
48/51/54
56/60/63
1090 x 710
1290 x 820
300
350
1133 x 754
1333 x 864
310
360
46
61
galvanised steel
8/16
8/16
40 (230V),3*16 (400V)
3*20
30
45
18,8
30,1
20,9
38,2
1,04
1,51
4,7
5,5
14,1
16,5
1800
2700
3000
4500
3600
5400
1 1/2"
1 1/2"
400/3/50
400/3/50
12
12
22,4
34,5
2
2
586*421*8
586*621*8
2
2
586*414*48
586*614*48
47/52/57
47/52/58
57/62/67
57/62/68
1290 x 970
1290 x 1090
450
650
1333 x 1008
1333*1133
460
660
76
118
8/25
8/25
3*25
3*25
UNT-PRC002-GB
AH-SVX03C-GB