Cabinet design
6.11 Power losses of the components
6.11
Power losses of the components
6.11.1
General information
The tables below provide an overview of the power loss of all components during rated
operation. The characteristic values apply for the following conditions:
● DC link voltage 700 V
● Pulse frequency of the Motor Modules 4 kHz
● Operating components at their rated power
The total losses of the relevant power unit are calculated from the power loss and the
corresponding electronics loss of the power unit.
6.11.2
Power loss for power units with internal air cooling
Table 6- 9
Single Motor Modules booksize C/D-type
3 A
5 A
9 A
18 A
30 A
Double Motor Modules booksize C/D-type
2 x 3 A
2 x 5 A
2 x 9 A
2 x 18 A
Note
Additional power loss values
The power loss data for other components in the booksize drive line-up can be found in the
SINAMICS S120 Manual "Booksize Power Units" (GH2).
116
Overview of power loss at rated operation for power units with internal air cooling (includ-
ing electronics losses)
Unit
W
W
W
W
W
W
W
W
W
Power loss
48.0
71.0
98.0
183.0
309.2
91.6
126.6
181.6
346.4
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1