2.5
System data
Unless explicitly specified otherwise, the following technical data is valid for components of
the SINAMICS S120 booksize drive system described in this document.
Table 2- 3
Electrical data
Line connection voltage
Line frequency
Electronics power supply
Short-circuit current rating SCCR according to UL508C
(up to 600 V)
Radio interference suppression
Overvoltage category
Degree of pollution
When using a motor holding brake, restricted voltage tolerances (24 V ±10 %) might need to be taken into account.
1)
The components must be protected against conductive pollution, e.g. by installing them in a control cabinet with degree
2)
of protection IP54 according to IEC 60529 or Type 12 according to NEMA 250. If conductive pollution can be excluded
at the installation site, a lower degree of cabinet protection may be permitted.
Table 2- 4
Modules
Motor Modules in booksize C/D-type format
DC link supply voltage
Rated pulse frequency
Table 2- 5
Degree of protection / protection class
Degree of protection
Protection class
Power circuits
Electronic circuits
Table 2- 6
Environmental conditions
Chemically active substances
Long-term storage
Transport
Operation
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1
380 ... 480 V 3 AC ±10 % (-15 % < 1 min)
47 ... 63 Hz
24 V DC -15/+20 %
SELV)
1.1 ... 447 kW: 65 kA
Category C2 acc. to EN 61800-3 (option)
for system versions in conformance with the documentation
III acc. to EN 61800-5-1
2 according to EN 61800-5-1, EN 61800-5-2
510 ... 720 V DC
4 kHz
At higher pulse frequencies, the corresponding characteris-
tic for current derating must be taken into consideration.
IPXXB according to EN 60529, open type according to
UL/CSA
I (with protective conductor connection)
safety extra-low voltage PELV/SELV
Class 1C2 according to EN 60721-3-1, in product packaging
Class 2C2 according to EN 60721-3-2, in transport packaging
Class 3C2 according to EN 60721-3-3
System overview
2.5 System data
, safety extra-low voltage (PELV or
1)
2)
1)
2)
35