5.6
Address space
The module can be configured differently; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the inputs.
Configuration options of AI 2xU/I 2-/4-wire HF
You can configure the module with STEP 7 (TIA Portal) or with a GSD file. If you configure the
module by means of a GSD file, the configurations are available under various short
designations/module names; see the table below. The following configurations are possible:
Table 5- 6
Configuration options with GSD file
Configuration
1 x 2-channel without value
status
1 x 2-channel with value
status
1 x 2-channel without value
status
1 x 2-channel with value
status
1 x 2-channel with value
status for module-internal
Shared Input with up to 4
submodules
1 x 2-channel with value
status and measured value
scaling
Value status (Quality Information, QI)
The value status is always activated for the following module names:
• AI 2xU/I 2-, 4-wire HF, QI,
• AI 2xU/I 2-, 4-wire HF, MSI
• AI 2xU/I 2-, 4-wire HF, SCALE
An additional bit is assigned to each channel for the value status. The value status bit
indicates whether the read in analog value is valid. (0 = value is incorrect).
Analog input module AI 2xU/I 2-/4-wire HF (6ES7134-6HB00-0CA1)
Equipment Manual, 05/21, A5E51055079-AA
Short designa-
tion/module name in
the GSD file
AI 2xU/I 2-, 4-wire HF
V1.0
AI 2xU/I 2-, 4-wire HF
V1.0, QI
AI 2xU/I 2-, 4-wire HF
V2.0
AI 2xU/I 2-, 4-wire HF
V2.0, QI
AI 2xU/I 2-, 4-wire HF
V2.0, MSI
AI 2xU/I 2-, 4-wire HF
V2.0, SCALE
Configuration software, e.g. with STEP 7 (TIA Portal)
Availability in hardware
catalog STEP 7 (TIA Portal)
Integrated as of STEP7 V13
Integrated as of STEP7 V13
•
HSP161 STEP7 V13 SP1
•
Integrated as of STEP7
V14
•
HSP161 STEP7 V13 SP1
•
Integrated as of STEP7
V14
•
HSP161 STEP7 V13 SP1
•
Integrated as of STEP7
V14
•
HSP161 STEP7 V13 SP1
•
Integrated as of STEP7
V14
Parameters/address space
5.6 Address space
GSD file
GSD file
PROFINET IO
PROFIBUS DP
X
X
X
---
X
X
X
---
X
---
X
---
37