Siemens SIMATIC ET 200SP Manual page 32

Analog input module ai 2xu/i 2-/4-wire hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Example
The following values result, for example:
Table 5- 4
Base measuring range
S7 format
Scaling of measured values
As shown in the table, -10 V corresponds to 1.00 and +10 V corresponds to 7.00.
Combination with measuring range adjustment
If the measuring range adjustment is enabled in addition to measured value scaling, first the
measuring range is scaled and then the representation of the measuring range. The table
below shows an example of the combination of measured value scaling and measuring range
adjustment.
Table 5- 5
Measuring range adjustment
S7 format
Scaling of measured values
As shown in the table, -4 V corresponds to 1.00 and +8 V corresponds to 7.00.
Analog input module AI 2xU/I 2-/4-wire HF (6ES7134-6HB00-0CA1)
Equipment Manual, 05/21, A5E51055079-AA
Example of measured value scaling
Low nominal range limit
-10 V
-27648
1.00
Example for a combination of measured value scaling and measuring range adjustment
Low nominal range limit
-4000 mV
-27648
1.00
Parameters/address space
5.5 Scaling of measured values
High nominal range limit
+10 V
+27648
7.00
High nominal range limit
8000 mV
+27648
7.00