AIRFLOW LABEL

Menu Navigation and Selection Instructions
Using Phone Application over Bluetooth Network:
1) Connect to the air handler (instructions provided by phone during
connection process).
2) Select desired settings menu
3) Select item that requires adjustment and make necessary selection
4) Submit Changes
Using On-Board Push Buttons:
1) Use the Right and Left Buttons to scroll between menus
2) Use the Center Button to select desired menu when menu code is
shown on 7-segment displays
3) Use the Left and Right Buttons to scroll through options within the
desired menu (the display will flash while scrolling through options for
selection)
4) Use the Center Button to select the displayed option (when selected
the display will stop flashing)
5) Use the Center Button to finalize selection and return to the main
menu
Profiles
1
2
3
4
Airflow Settings Instructions
1) For non-communicating installations, select the type of unit installed
in the OdS menu (1AC = single-stage air conditioner,
1HP = single-stage heat pump, 2AC = 2 stage air conditioner,
2HP = 2 stage heat pump) Default = OFF (no outdoor unit).
2) Use the Tonnage Menu (ton) to select Cooling/Heat Pump Airflow
(non-communicating installation). Tonnage selection options and
corresponding airflow CFM can be found to the right.
[Airflow = Tonnage Selection x 400] Default selection is 6.0 tons.
3) [Optional] Use the Cooling Trim Menu (CtF) to adjust the cooling
airflow from -10% to +10% (2% increments). This applies for 2
stage communicating outdoor units and single or 2 stage
non-communicating outdoor units. For inverter outdoor units use
Cooling Trim Factor High, Intermediate and Low menus (CtH, CtI,
and CtL) for trim adjustment.
4) [Optional] Use the Heating Trim Menu (HtF to adjust the heat pump
airflow from -10% to +10% (2% increments). This applies for 2
stage communicating outdoor units and single or 2 stage
non-communicating outdoor units. For inverter outdoor units use
Heating Trim Factor High, Intermediate and Low menus (HtH, HtI,
and HtL) for trim adjustment.
5) [Optional] Use the Constant Fan Menu (FSD) to select the
percentage of maximum airflow for continuous fan
6) [Optional] Use the Cooling Airflow Profile Menu (CAP) to select
between 4 cooling airflow profiles. Profile options 1-4 are listed above.
See installation manual for further details
Selecting Heater Kit: Use the Electric Heating Wattage Menu (EHt) to select heater kit size. See "Menu Navigation and Selection
Instructions" above. Default selection is 0 (No Heat Kit). Select installed heater kit for heater kit operation.
NR - Not Rated
Pre-Run
Short-Run
OFF Delay
--------
--------
60 sec/100%
--------
30 sec/50% 60 sec/100%
--------
7.5 min/82% 60 sec/100%
30 sec/50%
7.5 min/82% 60 sec/100%
Electric Heat Airflow Table
Htr Kw
MBVC1201AA-1
3
600
5
600
6
635
8
740
10
1000
15
1400
19
NR
20
NR
21
NR
25
NR
Tonnage Menu (t o n)
Tonnage
Airflow
Selection
1.0
400
1.1
440
1.2
480
1.3
520
1.4
560
1.5
600
1.6
640
1.7
680
1.8
720
1.9
760
2.0
800
2.1
840
2.2
880
2.3
920
2.4
960
2.5
1000
2.6
1040
2.7
1080
2.8
1120
2.9
1160
3.0
1200
3.1
1240
3.2
1280
3.3
1320
3.4
1360
3.5
1400
Maximum Airflow Output
MBVC1201AA-1
MBVC1601AA-1
1400
2000
*If airflow is set above the model's maximum value, the output will be the
maximum value
MBVC1601AA-1
MBVC2001AA-1
800
800
800
1000
1000
1500
NR
NR
NR
NR
18
Tonnage
Airflow
Selection
3.5
1400
3.6
1440
3.7
1480
3.8
1520
3.9
1560
4.0
1600
4.1
1640
4.2
1680
4.3
1720
4.4
1760
4.5
1800
4.6
1840
4.7
1880
4.8
1920
4.9
1960
5.0
2000
5.1
2040
5.2
2080
5.3
2120
5.4
2160
5.5
2200
5.6
2240
5.7
2280
5.8
2320
5.9
2360
6.0
2400
MBVC2001AA-1
2000
800
800
800
1000
1200
1500
NR
NR
NR
NR
0140A00706-A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents