Counterflow And Horizontal Applications; Electrical Connections; 208/230 Volt Line Connections; Low Voltage Wiring - Goodman MBVC 1 Series Installation Instructions Manual

Blower cabinet
Table of Contents

Advertisement

Figure 4 - Attic Installation
4. Attach return and supply ductwork. Seal connections.
5. Make electrical connections as specified in Electrical
Connections section of this manual.
Figure 5 - Hanging Installation

Counterflow and Horizontal Applications

Loosen motor mount and rotate motor (See Figure 6). Be sure mo-
tor is oriented with the female connections on the casing pointing
down. If the motor is not oriented with the connections pointing
down, water could collect in the motor and cause premature failure.
NOTE: After rotating motor, tighten motor mount to secure motor.
Be sure that the gap between the motor and the insulation is the
same as it was before loosening the motor mount. This will ensure
that the blower wheel is properly spaced inside the blower housing.
FRONT VIEW
FEMALE CONNECTIONS
Figure 6 - MBVC Motor Orientation
Support
Support
SIDE VIEW

Electrical Connections

Consult the local power company and local codes before installing
this unit. All wiring must be in accordance with the National Elec-
trical Code as well as all local codes. Knockouts have been provided
on side and top of the cabinet for the installation of the electrical
conduit. If the knockouts on the cabinet sides are used for electrical
conduit, an adapter ring must be used in order to meet UL1995
safety requirements. Use Minimum Circuit Ampacity and type of
wire to determine proper wire size. The unit MUST be properly
grounded. A ground lug is provided in the unit.
Check all factory connections before connecting electrical power
to unit to ensure none were loosened or disconnected during
shipping and handling.

208/230 Volt Line Connections

If heater kits will not be installed, remove the proper size knockout
for the electrical conduit connection. Connect electrical conduit to
the unit using two washers to make an approved connection. If the
high voltage knockout is removed, please use the provided foam
tape to seal the opening with the conduit.
The power supply wires must be connected to the red and black
power wiring. Two wire nuts are provided in the bag assembly for
this connection. Wrap the wire nuts with electrical tape. (Insulat-
ed crimp type connectors, field supplied, may be substituted for
the wire nuts and electrical tape provided proper size connectors
are used.) A ground wire MUST be connected to the ground lug
inside the unit.

Low Voltage Wiring

A 24V-control voltage connects the air handler to the room thermo-
stat and condenser and must use low voltage wiring with copper
conductors. A minimum 18 AWG wire must be used for installations
up to 150 feet. Low voltage wiring must be connected through
the top of the cabinet or either side. If the low voltage opening is
being used, please replace the pre-installed cap with the bushing
provided in the literature kit.
HIGH VOLTAGE!
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO
,
ELECTRICAL SHOCK
DISCONNECT THE ELECTRICAL
POWER BEFORE ELECTRICALLY CONNECTING THE UNIT
T
O AVOID THE RISK OF FIRE OR EQUIPMENT DAMAGE
.
CONDUCTORS
T
O AVOID THE RISK OF PERSONAL INJURY
BE PROPERLY POLARIZED AND GROUNDED
A
LL WIRING MUST COMPLY WITH APPLICABLE LOCAL AND NATIONAL
. T
CODES
YPE AND LOCATION OF FUSED DISCONNECT SWITCH
COMPLY WITH ALL APPLICABLE CODES AND PROVIDE OVERCURRENT
PROTECTION AS SHOWN ON THE NAMEPLATE
5
WARNING
.
WARNING
,
USE COPPER
CAUTION
,
WIRING TO THE UNIT MUST
.
WARNING
(
ES
.
)
MUST