[sccommlg-270618, 1, en_US]
Figure 8-30
Deletability
The communication logs of your SIPROTEC 5 device can be deleted. Read details about this in chapter
8.5.12 Saving and Deleting the
Configurability
The communication logs are not freely configurable. The entries are preconfigured.

Communication-Supervision Log

8.5.10
The communication-supervision log is used to log communication events.
The following events are currently logged:
Status for each GOOSE subscription (if configured)
A log is kept of whether the GOOSE subscription has received valid messages or not.
Aggregated status for all GOOSE subscriptions
The status is TRUE if at least one GOOSE subscription does not receive any valid message.
Subscriber in simulation mode
GOOSE messages are processed with a simulation flag. The status is TRUE if at least one GOOSE subscrip-
tion processes simulated messages.
Reading from the PC with DIGSI 5
To reach the communication-supervision log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Com supervision log
The status of the communication-supervision log last loaded from the device is shown.
To update (synchronization with the device), click the button Read log entries in the headline of the
indication list.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Reading the Communication Log on the On-Site Operation Panel of the Device
Logs.
Operation in the Operating State