[sccommlg-270618, 1, en_US]
Figure 8-30
Deletability
The communication logs of your SIPROTEC 5 device can be deleted. Read details about this in chapter
8.5.12 Saving and Deleting the
Configurability
The communication logs are not freely configurable. The entries are preconfigured.
Communication-Supervision Log
8.5.10
The communication-supervision log is used to log communication events.
The following events are currently logged:
•
Status for each GOOSE subscription (if configured)
A log is kept of whether the GOOSE subscription has received valid messages or not.
•
Aggregated status for all GOOSE subscriptions
The status is TRUE if at least one GOOSE subscription does not receive any valid message.
•
Subscriber in simulation mode
GOOSE messages are processed with a simulation flag. The status is TRUE if at least one GOOSE subscrip-
tion processes simulated messages.
Reading from the PC with DIGSI 5
•
To reach the communication-supervision log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Com supervision log
The status of the communication-supervision log last loaded from the device is shown.
•
To update (synchronization with the device), click the button Read log entries in the headline of the
indication list.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Reading the Communication Log on the On-Site Operation Panel of the Device
Logs.
Operation in the Operating State
8.5 Logs
171