Siemens SIPROTEC 5 Manual page 191

V8.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

[ScZtkonf-040718, 1, en_US]
Figure 8-46
Settings on the Device Using the On-Site Operation Panel
You can only access some of the settings using the on-site operation while the device is being operated. To
reach the settings for time synchronization from the main menu, use the navigation keys on the on-site opera-
tion panel.
Select Main menu → Parameter → General → Time sync.
[sctimsyc-080413-01.tif, 1, en_US]
Figure 8-47
Configure up to 2 external time sources. There are port and channel numbers in communication inter-
faces for every configured time source. This depends on the configured hardware of your SIPROTEC 5
device.
Select the time-zone arrangement (UTC or local) for each time source.
Select the time by which time synchronization failures should be logged.
For each change in the settings, select the desired menu item and press the Change softkey.
Enter the changes and then confirm the entry by selecting the Ok softkey.
You will find application and setting information in the System Functions Device manual.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Time Settings via DIGSI 5
Time-Synchronization Settings
Operation in the Operating State
8.8 Change Device Settings
191