Operation in the Operating State
8.8 Change Device Settings
Online Settings via DIGSI 5
You should always use the online setting if you want to change individual function settings of a device in
operation. To reach the function settings of your SIPROTEC 5 device, use the project-tree window.
•
Select Online access → Interface → Device → Settings
Settings on the Device Using the On-Site Operation Panel
Using the on-site operation panel you can access function settings while the device is in operation. To reach
the function settings from the main menu, use the navigation keys on the on-site operation panel.
If multiple settings groups (see chapter
you are making your changes in the correct settings group. You can change this as necessary.
•
To do this, select Settings → General → Change group settings in the main menu
When the correct settings group is selected, proceed as follows:
•
Select Main menu → Settings → Function group → Function → Function block
The active settings of the selected function are displayed in the device display.
•
To select the parameter to be changed use the navigation keys or the number keys for direct selection
according to the right sidebar.
[scaswfnk-080413-02.tif, 1, en_US]
Figure 8-58
•
To change a parameter setting, click Change in the base bar dialog.
•
If you are not yet authorized to access via LOGIN, you will be requested to input the confirmation ID.
•
Use the number keys to enter the confirmation ID and confirm with Ok.
•
For the selection of settings, use the navigation keys to select a value from the displayed list of possible
settings.
•
For decimal parameters, you can input the setting value directly using the number keys within the
displayed setting range.
•
Confirm your settings using Ok or Enter. Setting values that are not permitted are declined.
•
To activate all changes made, press the left navigation key until you are prompted in the base bar to
confirm or cancel the changes.
•
Confirm your changes using Ok.
[scbstubn-080413-01.tif, 1, en_US]
Figure 8-59
198
8.8.9 Settings Group
Changing and Selecting Function Settings on the On-Site Operation Panel
Confirming Taking Over of Function Settings on the On-Site Operation Panel
Switching) have been activated, first ensure that