Using On-Site Operation Panel

5.7 Displaying Device Mode

5.7
Displaying Device Mode
Not Initialized Device (As-Delivered Condition)
SIPROTEC 5 devices are not initialized in the as-delivered condition. If a non-initialized device is connected to
the auxiliary voltage and started, then the following information is shown on the display:
Device variant
Firmware version
Serial number
Prompt Initialize device
NOTE
i
i
You may only initialize the device via DIGSI 5 and only then via the USB connection of your SIPROTEC 5
device.
See chapter
9 Commissioning
Initialized Device
The device can be in the following modes:
Commissioning mode
Simulation mode
Process mode
Fallback mode
In normal operation (process mode), the device is presented as described in chapter
NOTE
i
i
The device can change mode during commissioning, testing or in the event of a device failure. The mode
deviating from normal operation is shown respectively in the title bar of the device display. The name of
the mode is shown flashing in the top line of the device display (except in fallback and process mode):
Commissioning mode
Simulation mode
Take note of the information about these modes in chapter
On-the-Spot Assistance and
Commissioning Mode
The commissioning mode of the SIPROTEC 5 device allows you to check the existing wiring without affecting
or blocking the protection functions or other functions of the device. You can select the commissioning mode
manually.
You can find more information in Chapter
In commissioning mode, you can also check the communication with system-control technology. You can
generate test signals with the communication test in DIGSI by setting signals to be transmitted systematically
in the transmitter and checking their receipt.
You can find more information in chapter
Simulation Mode
In the simulation mode of the device, you can check the correct setting of protection functions and the
routing of signals. You can perform simple checks without wiring or using DIGSI. To do so, connect the device
90
for more information on initializing and commissioning.
Test.
9.2.2 Testing Current and Voltage
9.4.3 Testing Interfaces in the Compound
5.4 Structure of the Menu
9 Commissioning
and chapter
Inputs.
System.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
10 Maintenance,