AMI Deltacon Power
Program List and Explanations
5.3.2.32.31
5.3.2.32.1
5.3.2.32.22
5.3.2.32.32
5.3.2.32.4
5.3.2.1
5.3.2.24
5.3.2.340
5.3.2.44
5.3.2.54
5.3.2.6
5.3.2.7
5.3.2.1
5.3.4
74
Control Parameters
Range for each Parameter same as
Actuator = Motor valve
Dosing is controlled by the position of a motor driven mixing valve.
Run time: Time needed to open a completely closed valve
Range: 5–300 Sec.
Neutral zone: Minimal response time in % of the runtime. If the re-
quested dosing output is smaller than the response time, no change
will take place.
Range: 1–20 %
Control Parameters
Range for each Parameter same as
Function = Timer:
The relay will be activated repetitively depending on the programmed
time scheme.
Mode: Operating mode (interval, daily, weekly)
Interval/Start time/Calendar: Dependent on options operating mode.
Run time: time the relay stays active.
Range: 5–32'400 Sec
Delay: during run time plus the delay time the signal and control out-
puts are held in the operating mode programmed below.
Range: 0–6'000 Sec
Signal Outputs: select the behavior of the signal outputs when the re-
lay closes. Available values: cont., hold, off
Output/Control: select the behavior of the control outputs when the
relay closes. Available values: cont., hold, off
Function = Fieldbus:
The relay will be switched via the Profibus input. No further parame-
ters are needed.
Input: The functions of the relays and signal outputs can be defined
depending on the position of the input contact, i.e. no function,
closed or open.
5.2.1.43, p. 66
5.2.1.43, p. 66
A-96.250.451 / 190121