Swann AMI Deltacon Power Operator's Manual page 67

Monitoring system
Table of Contents

Advertisement

AMI Deltacon Power
Program List and Explanations
5.2.1.43
5.2.1.43.13
5.2.1.43.23
5.2.1.43
5.2.1.43.14
5.2.1.43.24
5.2.1.43
5.2.1.43.16
5.2.1.43.26
5.2.1.43
5.2.1.43.17
5.2.1.43.27
5.2.1.43
5.2.1.43.18
5.2.1.43.28
5.2.1.43
5.2.1.43.19
5.2.1.43.29
5.2.1.43.3
5.2.1.43.4
A-96.250.451 / 190121
Control Parameters: if Parameters = Temp.1
Setpoint
Range: -25 to +270 °C
P-Band:
Range: -25 to +270 °C
Control Parameters: if Parameters = Temp. 2
Setpoint
Range: -25 to +270 °C
P-Band:
Range: -25 to +270 °C
Control Parameters: if Parameters = Difference
Setpoint
Range: 0.000 –3000 S
P-Band:
Range: 0.000 –3000 S
Control Parameters: if Parameters = Sample flow
Setpoint
Range: 0.0 –20 l/h
P-Band:
Range: 0.0 –20 l/h
Control Parameters: if Parameters = pH
Setpoint
Range: 0.00 –14 pH
P-Band:
Range: 0.00 –14 pH
Control Parameters: if Parameters = Ammonia
Setpoint
Range: 0.00 –500 ppm
P-Band:
Range: 0.00 –500 ppm
Reset time: The reset time is the time till the step response of a sin-
gle I-controller will reach the same value as it will be suddenly
reached by a P-controller.
Range: 0–9'000 sec
Derivative time: The derivative time is the time till the ramp response
of a single P-controller will reach the same value as it will be sudden-
ly reached by a D-controller.
Range: 0–9'000 sec
67