Table 1.
Table 2.
Resistance applied to RTM MODE

Compressor Modules

(SCM & MCM - 1U49 standard on all units)
The compressor modules, (Single Circuit & Multiple Circuit), upon receiving a request for
mechanical cooling, energizes the appropriate compressors and condenser fans. It monitors the
compressor operation through feedback information it receives from various protection devices.

Human Interface Module

(HI - 1U65 standard on all units)
The Human Interface module enables the operator to adjust the operating parameters for the unit
using it's 16 key keypad. The 2 line, 40 character LCD screen provides status information for the
various unit functions as well as menus for the operator to set or modify the operating parameters.

Heat Module

(1U50 used on heating units)
The Heat module, upon receiving a request for Heating, energizes the appropriate heating stages
or strokes the Modulating Heating valve as required.
14
RTM Resistance Input vs. Setpoint Temperatures
RTM cooling or heating
setpoint input used
as the source for
a ZONE temp setpoint (°F)
40
45
50
55
60
65
70
75
80
n/a
n/a
RTM Resistance Value vs. System Operating Mode
input Terminals (Ohms)
Max. Tolerance 5%
2320
4870
7680
10770
13320
16130
19480
27930
RTM cooling setpoint input
used as the source
for SUPPLY AIR temp
setpoint cooling (°F)
40
45
50
55
60
65
70
75
80
85
90
Constant Volume Units
Fan Mode
Auto
Auto
Auto
On
On
On
Auto
On
Resistance (Ohms) Max.
Tolerance 5%
1084
992
899
796
695
597
500
403
305
208
111
System Mode
Off
Cool
Auto
Off
Cool
Auto
Heat
Heat
RT-SVX36G-EN

Hide quick links: