Trane IntelliPak SAHL Series Installation, Operation And Maintenance Manual page 183

Commercial single-zone rooftop air conditioners with cv, vav, or szvav controls
Table of Contents

Advertisement

Suction Line Filter/Drier
Figure 96. Suction line filter/drier installation
Table 69. Supply and exhaust/return fan VFD programming parameters
Limits & Warnings
Note: These parameters are motor specific and the actual motor nameplate rating must be used. Do not use the unit name
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable frequency drives or other energy storing
components provided by Trane or others, refer to the appropriate manufacturer's literature for
allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that
all capacitors have discharged. Failure to disconnect power and discharge capacitors before
servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN.
RT-SVX36G-EN
Menu
Parameter
1-21
1-22
Load & Motor
1-24
1-25
215
plate values.
CONDENSER - SUCTION
FILTER / DRIER PLACEMENT
There is a min. 16" straight distance
from the Tee (Elbow) to anything in this line.
Description
Setting
Set Based on Motor
Motor Power
Nameplate
Set Based on Motor
Motor Voltage
Nameplate
Set Based on Motor
Motor Current
Nameplate
Set Based on Motor
Motor Speed
Nameplate
Current Limit
100% Rated Current Limits the maximum current to motor
WARNING
Maintenance
Description
Set only for applications using 3hp
motors
Set to 2.2kW/3hp
Set only for 200/230v 60hz & 380/415
50Hz applications
Sets the motor FLA
Sets the motor RPM
183