Remove Evaporative Condenser Fan Shipping Brackets - Trane IntelliPak SAHL Series Installation, Operation And Maintenance Manual

Commercial single-zone rooftop air conditioners with cv, vav, or szvav controls
Table of Contents

Advertisement

Installation
2. Using two #10-32 x 1-3/4" screws provided, install the sensor's mounting bracket to the factory
3. Using the #10-32 x 1/2" screws provided, install the O/A static pressure sensor vertically to the
4. Remove the dust cap from the tubing connector located below the sensor in the vertical
5. Attach one end of the 50' x 3/16" O.D. factory provided pneumatic tubing to the sensor's top
Units with Statitrac:
6. Open the filter access door, and locate the DSP control devices illustrated in

Remove Evaporative Condenser Fan Shipping Brackets

To remove shipping brackets
Important: Remove fan shipping brackets before startup. Failure to remove brackets could result
Evaporative condensers are shipped with fan shipping brackets to reduce damage caused by
vibration during shipment. The fan shipping brackets must be removed prior to unit startup.
To remove the shipping brackets start from the side opposite to the drain actuator
(see
1. Loosen the screw for the bracket that holds the inlet louvers below the door side.
2. Remove inlet louvers and set to the side.
Note: Service technician may need to step on the horizontal surface of FRP coated base.
3. Unscrew the bolt in the middle of the door. Keep the bolt in a safe place.
4. Lift one door with handle until it touches the top. Swivel bottom of door to remove it from the
5. Slide and remove the middle mist eliminator section so that the shipping bracket is visible.
6. Use screw gun to unscrew the two screws that hold the fan shipping bracket. The bracket should
7. Go to the other side of the unit and follow the procedure for inlet louver and door removal
8. Hold the bracket with one hand and remove remaining two screws.
9. Remove the bracket and all the removed screws from the unit.
Important: Make sure there are no screws remaining in the coil area.
10. Reinstall inlet louvers, mist eliminators and louvers.
Check that the direction of arrow on the inlet louver is correct.
54
installed bracket (near the filter section).
sensor bracket.
support.
port, and the other end of the tubing to the connector in the vertical support. Discard any excess
tubing.
are three tube connectors mounted on the left of the solenoid and transducers. Connect one
end of the field provided 3/16" O.D. pneumatic tubing for the space pressurization control to
the bottom fitting. Route the opposite end of the tubing to a suitable location inside the building.
This location should be the largest open area that will not be affected by sudden static pressure
changes.
in fan damage.
Figure 60, p.
141):
Step with care.
door opening and set it to the side.
drop down but still remain engaged with a hook on the bracket.
(see steps 1 - 6).