Trane IntelliPak SAHL Series Installation, Operation And Maintenance Manual page 82

Commercial single-zone rooftop air conditioners with cv, vav, or szvav controls
Table of Contents

Advertisement

Installation
FIRE
The UCM network relies on various sensors located throughout the system to provide temperature
information in the form of an analog input. All of the sensors used have the same temperature vs.
resistance co-efficient and are made from Keystone Carbon D97 material with a 1 degree
Centigrade tolerance.
Table 30.
Temperature (°F)
82
– Exhaust/Return Dampers - Closed (if equipped)
– OA Dampers - Closed
– Heat - All heat stages Off (staged gas and elec.), Hydronic
– Heat & Mod Gas Heat output at 0%.
– Occupied/Unoccupied output - De-energized
– VO Relay - Energized (with VOM module installed)
– OA Preheater State - Off (with VCM module installed)
– Supply Fan - Off
– Inlet Vanes - Closed (if equipped)
– Exhaust/Return Fan - Off (if equipped)
– Exhaust/Return Dampers - Closed (if equipped)
– OA Dampers - Closed
– Heat - All heat stages Off (staged gas and elec.), Hydronic
– Heat & Mod Gas Heat output at 0%.
– Occupied/Unoccupied output - De-energized
– VO Relay - Energized (with VOM module installed)
– OA Preheater State - Off (with VCM module installed)
Temperature vs. resistance coefficient
Resistance
(in. 1000 Ohms)
-40
-30
-20
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
66
67
68
69
70
Temperature (°F)
346.1
71
241.7
72
170.1
73
121.4
74
103
75
87.56
76
74.65
77
63.8
78
54.66
79
46.94
80
40.4
85
34.85
90
30.18
100
26.22
105
22.85
110
19.96
120
17.47
130
15.33
140
13.49
150
13.15
160
12.82
170
12.5
180
12.19
190
11.89
200
Resistance
(in. 1000 Ohms)
11.6
11.31
11.03
10.76
10.5
10.25
10
9.76
9.53
9.3
8.25
7.33
5.82
5.21
4.66
3.76
3.05
2.5
2.05
1.69
1.4
1.17
0.985
0.83
RT-SVX36G-EN