Charge the new oil into the Schrader valve on the
shell of the compressor. Due to the moisture
absorption properties of POE oil, do not use POE oil
from a previously opened container. Also discard
any excess oil from the container that is not used.
CSHN Compressors (75 & 89-130 Ton)
CSHN compressors have an oil drain valve, See
Figure
the compressor. After the refrigerant has been
recovered, pressurize the system with nitrogen to
help remove the oil from the compressor.
Charge the new oil into the Schrader valve or oil drain valve on the shell of the compressor. Due
to the moisture absorption properties of POE oil, do not use POE oil from a previously opened
container. Also discard any excess oil from the container that is not used.
Figure 94. CSHN
Table 66. Oil charge per compressor
Compressor
CSHD 092
CSHD 110 thru 183
CSHN 176 thru 315
Table 67. Torque requirements for rotolock fittings
CSHD*
CSHN*
Note: Always replace gasket when reassembling oil equalizer lines.
RT-SVX36G-EN
94, which allows the oil to be drained out of
Oil equalizer Rotolock
connection fitting
¼ Schrader port
Oil drain valve
Pints
6.3
7.0
14.2
64
+/- 12 ft-lbs
100 +/- 10 ft-lbs
Figure 93. PTFE gasket