General
Topology
As a line coupler, the device connects a line with a main line. As an area coupler, the line coupler S
connects a main line with an area line. Each line requires its own power supply.
Backbone = Area line with up to 15 area couplers, physical address x.0.0
Main Line = Main line with up to 15 line couplers, physical addres x.y.0
Line = Line with up to 64 devices including the line coupler. Up to 256 devices are possible when up to
three line repeaters are used.
The function of the device is assigned by the assignment of the physical address.
Note
If a second output of the Power Supply SV/S is used for connection, a DV/S choke must be connected.
For further information refer to the Power supply product manual