Summary of Contents for Theben Line coupler S KNX

  • Page 1 Linienkoppler S KNX Line coupler S KNX Line coupler S KNX 9070880 Status: March 16 (Subject to change) Page...
  • Page 2: Table Of Contents

    Line coupler S KNX Contents Page Contents General ....................3 Using the product manual ......................3 1.1.1 Structure of the product manual ....................3 1.1.2 Notes ............................4 Product and functional overview ....................5 1.2.1 Line/area coupler ......................... 5 1.2.2 Repeater ............................
  • Page 3: General

    General The Theben Line Coupler S KNX is a modular installation device with a module width of 2 space units. It is used as a line or area coupler or as a repeater. As a line coupler, the Line coupler S connects a line with a main line, as an area coupler it connects a main line with an area line.
  • Page 4: Notes

    Line coupler S General 1.1.2 Notes Notes and safety instructions are represented as follows in this manual: Note Tips for usage and operation Examples Application examples, installation examples, programming examples Important These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury.
  • Page 5: Product And Functional Overview

    Line coupler S General Product and functional overview The Line Coupler Line Coupler S can be used as a line/area coupler or as a repeater. 1.2.1 Line/area coupler As a line/area coupler, the Line Coupler S connects the data flow of two lines but isolates them electrically. The coupler can route physically addressed, group addressed as well as broadcast telegrams.
  • Page 6 Line coupler S General Topology As a line coupler, the device connects a line with a main line. As an area coupler, the line coupler S connects a main line with an area line. Each line requires its own power supply. Line coupler S Line coupler S Line coupler S...
  • Page 7: Repeater

    Line coupler S General 1.2.2 Repeater As a repeater, the Line coupler S connects the data flow of two line segments but isolates them electrically. Behind a line coupler (in one line), up to three repeaters can be connected in parallel in a line. This is how up to four line segments form an entire line.
  • Page 8 Line coupler S General Topology Up to three repeaters are connected in parallel in a line. Each line segment requires its own power supply. Line coupler S Line coupler S Line coupler S Line coupler S Main Line = Main line with up to 15 line couplers Line = Line with up to three repeaters Line Segment = Line segment, per segment up to 64 devices are possible (in total up to 256 devices are possible) including the repeater.
  • Page 9: Device Technology

    Line coupler S Device technology Device technology The Theben Line Coupler S KNX is a If required, the Line coupler S filters modular installation device with a module telegrams and only routes the telegrams width of 2 space units. intended for other lines. It is possible to...
  • Page 10 Line coupler S Device technology Temperature range Operation -5 °C…+45 °C Storage -25 °C…+55 °C Transport -25 °C…+70 °C Ambient conditions Maximum air humidity To EN 50 491 95 %, no condensation allowed Design Modular installation device (MDRC) Modular installation device, Pro M Dimensions 90 x 36 x 64.5 mm (H x W x D) Mounting width...
  • Page 11 The ETS and the current version of the device application program are required for programming. The current application program can be found with the respective software information for download on the Internet at www.theben.de/downloads. After import it is available in the ETS under Theben AG/System components/...
  • Page 12: Circuit Diagram

    Line coupler S Device technology Circuit diagram Line coupler S Label carrier Button Programming LED Programming (red) Bus connection terminal of the primary/main line Bus connection terminal of the secondary line (yellow) (yellow) (green) Note The main and secondary lines must each be supplied with power from separate power sources (electrically isolated).
  • Page 13: Dimension Drawing

    Line coupler S Device technology Dimension drawing Line coupler S Status: March 16 (Subject to change) Page...
  • Page 14: Assembly And Installation

    Line coupler S Device technology Assembly and installation The Line coupler S is a modular installation device for quick installation in the distribution board on 35 mm mounting rails to EN 60 715. The Line coupler S mounting position can be selected as required. The connection to the bus is established using the supplied bus connection terminals.
  • Page 15: Display Elements

    Line coupler S Device technology 2.4.1 Display elements Indicator LEDs are located on the front of the Line coupler S. The response of the display elements is described in the following table: KNX operation OFF: The Line coupler S is not operational. No power supply is applied or it has malfunctioned.
  • Page 16: Commissioning

    The parameterization of the Line coupler S is undertaken using application program Couple Repeat/2, Couple/1 or Repeat/1 and the Engineering Tool Software ETS. The application program can be found at Theben AG/System components/... For parameterization purposes, a PC or Laptop with ETS and a connection to the KNX, e.g. via RS232, USB or IP interface, is required.
  • Page 17: Parameters

    The parameterization of the Line coupler S is implemented using the Engineering Tool Software ETS. The application program can be found in the ETS at Theben AG/System components/... The following chapter describes the parameters of the Line coupler S using the parameter windows. The parameter windows feature a dynamic structure, so that further parameters may be enabled depending on the parameterization and the function.
  • Page 18: Parameter Window General

    Line coupler S Commissioning 3.2.1.1 Parameter window General The device functions are defined in this parameter window. Device function Options: Line/Area Coupler Repeater • Line/Area Coupler: The data flow between two lines is connected. Both lines are electrically isolated from one another. The Parameter window Main line -->...
  • Page 19: Device Function - Line/Area Coupler

    Line coupler S Commissioning 3.2.1.2 Device function - Line/Area Coupler 3.2.1.2.1 Parameter window Main line --> Line This parameter window is visible if in Parameter window General, page 18, the device function Line/Area Coupler has been selected. In this parameter window, the settings for the connection from the primary/main line to the line are undertaken.
  • Page 20 Line coupler S Commissioning Broadcast telegrams Options: route block Broadcast telegrams are used, for example, by the ETS to identify KNX devices in programming mode. • route: Broadcast telegrams are routed. • Block: Broadcast telegrams are blocked. In case of errors repeat telegrams Options: user-defined •...
  • Page 21 Line coupler S Commissioning Telegram confirmation Options: only if routed always • only if routed: Telegrams that are routed are acknowledged. • always: Every telegram is acknowledged. The following applies with a group address view: Main groups 0…13 => 1…28,671 Main groups 14…31 =>...
  • Page 22: Parameter Window Line --> Main Line

    Line coupler S Commissioning 3.2.1.2.2 Parameter window Line --> Main line This parameter window is visible if in Parameter window General, page 18, the device function Line/Area Coupler has been selected. In this parameter window, the telegram functions for the connection from a secondary line to the primary/main line are defined.
  • Page 23: Device Function Repeater

    Line coupler S Commissioning 3.2.1.3 Device function Repeater 3.2.1.3.1 Parameter window Settings This parameter window is visible if in Parameter window General, page 18, the device function Repeater has been selected. In case of errors repeat group addressed telegrams on main line Options: •...
  • Page 24: Applications For The Ets 3

    Line coupler S Commissioning 3.2.2 Applications for the ETS 3 The applications Couple/1.x and Repeat/1.x can be loaded in the Line coupler S via the ETS 3. 3.2.2.1 Application Couple/1.x, parameter window Settings In this parameter window, the settings for the Area/Line Coupler are defined. Group telegrams main group 0...13 Main line -->...
  • Page 25 Line coupler S Commissioning Group telegrams main group 14...31 Options: route block • route: All group telegrams are routed. • Block: All group telegrams are blocked. In case of errors repeat group addressed telegrams on main line In case of errors repeat group addressed telegrams on line Options: •...
  • Page 26: Application Repeat/1X

    Line coupler S Commissioning 3.2.2.2 Application Repeat/1x 3.2.2.2.1 Parameter window Settings In this parameter window, the settings for the function Repeater are undertaken. In case of errors repeat group addressed telegrams on main line Options: • yes: If an error is detected when a group addressed telegram is transmitted on the main line, the telegram is repeated up to three times.
  • Page 27: Appendix

    Line coupler S Commissioning Appendix Scope of delivery The Theben AG Line coupler S is supplied together with the following components. Please check the items received using the following list. • 1 x Line coupler S • 1 x installation and operating instructions •...
  • Page 28: Manual

    Line coupler S Manual Manual Status: March 16 (Subject to change) Page...
  • Page 29 Line coupler S Manual Status: March 16 (Subject to change) Page...