Device Function - Line/Area Coupler; Parameter Window Main Line --> Line - Theben Line coupler S KNX Manual

Table of Contents

Advertisement

Line coupler S
Commissioning
3.2.1.2

Device function - Line/Area Coupler

3.2.1.2.1
Parameter window Main line --> Line
This parameter window is visible if in Parameter window General, page 18, the device function Line/Area
Coupler has been selected.
In this parameter window, the settings for the connection from the primary/main line to the line are
undertaken.
Group telegrams main group 0...13
Group telegrams main group 14...31
Option:
filter: Only group telegrams entered into the filter table are routed. The ETS automatically creates the
filter table.
route: All group telegrams are routed.
Block: All group telegrams are blocked.
Physically addressed telegrams
Option:
filter: Physically addressed telegrams (programming telegrams) are routed according to the topology.
block: Physically addressed telegrams are blocked.
Status: March 16 (Subject to change)
filter
route
block
filter
block