Emergency Off, Emergency Ventilation and Generator Run Connections
The LC6000-200 controller is shipped with emergency off, emergency ventilation and generator run contacts. There
are factory-installed jumpers across terminals #6 and #7 (emergency off), #8 and #9 (emergency ventilation) and
#10 and #11 (generator run). Remove the factory-installed jumpers before making the connections.
LC6000-200 Series Connection for Emergency Off, Emergency Ventilation and Generator Run (If Applicable)
3
4
5
Manual 2100-704C
Page
28 of 47

FIGURE 25

8
9
10
11
12
6
7
13
16
18
19
14
15
17
Generator Run*
Emergency Ventilation*
Emergency Off*
* Normally closed (NC) contacts required.
By default:
Closed = No Alarm
Open = Alarm
20