Figure 28 - Bard FUSION-TEC WR Series Literature Assembly

Сsystem/wall-mount air conditioner with lc6000-200 supervisory controller
Hide thumbs Also See for FUSION-TEC WR Series:
Table of Contents

Advertisement

Placement of Communication Wire Filters (Daisy Chain and Alternate Methods)
Place filter here
LC6000
Place filter here
Unit 1
NOTE: Line filters can be on either the unit or controller, whichever device is on the end of the chain. No matter
how many units there are, the two end devices will only have ONE communication cable, whereas the
center devices will all have TWO (as shown above). Maximum two wires in each terminal. Filters go inside
the unit or controller; shown out of unit above for identification only.
Manual 2100-704C
Page
30 of 47

FIGURE 28

Daisy Chain Wiring (up to 14 units)
Unit 1
Alternate Wiring (up to 14 units)
Unit 2
Unit 2
Unit 3
LC6000
Place filter here
Unit 4...up to
14 units
Place filter here
Unit 3
Unit 4...up to
14 units