Communication Wiring

Connect the communication wiring from the wall-mount units to the controller in the manner shown in Figures 26,
27 or 28. The daisy chain does not need to follow the addressing order. The communication wire should be 2-wire,
18 gauge shielded cable with drain. Any color can be used. Be sure to match "+" and "-" symbols on controller
terminal blocks to unit control terminal block (see Figures 30 and 31 on pages 32 and 33). Attach communication
wire filters as shown in Figures 26, 27 or 28. Filters go inside the unit or controller box; they are shown out of
unit for identification purposes only. Do not run communication wiring in same conduit as supply wiring. Route
communication wiring and power supply wiring in their own separate conduits.
Wall-Mount Unit
In addition to the "daisy chain" method of connecting the communication wiring shown in Figure 26, the wall-mount
units can also be connected in the manner shown in Figure 27. If connecting wall-units this way, be sure to place
the communication wire filters in the positions shown in Figure 27. See Figure 2 on page 30 for more information on
the correct placement of the communication wire filters depending on the wiring method used.
Wall-Mount Unit
Communication Wiring (Daisy Chain Method)
Wall-Mount Unit
Filter
Communication Wiring (Alternate Method)
Controller
Filter
FIGURE 26
FIGURE 27
LC
LC6000 Controller
Filter
Wall-Mount Unit
Manual 2100-704C