Section 6 - Technical data
Placement on a level surface of free of
obstructions (including snow, for winter
operation) or air circulation ensures rated
performance, reliable operation, and ease
of maintenance. Site restrictions may
compromise minimum clearances indi-
cated below, resulting in unpredictable
airflow patterns and possible diminished
performance.

Figure 35 - Dimensions, 2 and 3 compressor SI, YCIV0157E/V and YCIV0157S/P/H

116

Dimensions - 2 and 3 compressor SI

Models YCIV0157E/V and YCIV0157S/P/H
1 1/2"
POWER ENTRY
POWER ENTRY
10" WIDE X 13"
10" WIDE X 13" HIGH
4"
HIGH
VIEW B-B
POWER ENTRY IS ON BOTTOM OF PANEL
B
YCIV
A
0157E/V
19.1"
0157S/P/H
17.4"
CONTROL ENTRY
3" WIDE X 13 1/2" HIGH
C
B
C
A
(EDGE OF UNIT
TO COOLER
CONNECTION)
B
C
28.1"
84.5"
29.1"
90.0"
Johnson Controls unit controls will op-
timize operation without nuisance high-
pressure safety cutouts; however, the
system designer must consider potential
performance degradation. Access to the
unit control center assumes the unit is no
higher than on spring isolators. Recom-
mended minimum clearances: side to wall
– 2 m; rear to wall – 2 m; control panel to
end wall – 1.2 m; top – no obstructions
whatsoever; distance between adjacent
units – 3 m. No more than one adjacent
wall may be higher than the unit.
Form 201.23-NM2
Issue date: 12/19/2023
1 3/4"
12"
VIEW C-C
B
88 1/8"
VIEW A-A
D
112.8"
110.1"
Johnson Controls