Dimensions - Ycal0041 (Si) - York YCAL0065 User Manual

Air-cooled scroll chillers style d 50 and 60hz 47 – 60 ton 165 – 210 kw
Table of Contents

Advertisement

Dimensions -
1213
Aluminum
Center of Gravity (in.)
YCAL
X
0041
1513.7
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
46
YCAL0041 (SI)
171
82
100
VIEW B-B
BOTTOM OF PANEL
1192
LIQUID OUT
2292 BASE WIDTH
Y
1107.0
22 TYP.
LIQUID IN
76 VICTAULIC (typ)
1146
LEFT END
YCAL
ELECTRICAL ACCESS
PANEL
879
252
401
321
Copper
Center of Gravity (in.)
X
0041
1616.1
YORK INTERNATIONAL
Y
1111.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ycal0041Ycal0045Ycal0051Ycal0055Ycal0061

Table of Contents