Copyright © 2015, Juniper Networks, Inc.
Figure 33: Three-Phase Delta AC Power Cord
NOTE:
The three-phase delta AC PDM terminal blocks will be flipped
depending on which slot the PDM gets plugged into.
CAUTION:
Wire label configuration is for Juniper Networks supplied cable
only. If you are using your own cable, make sure that you use the proper
connections.
To connect wires to the terminal block that serves three PSMs:
a. Insert the grounding wire into the grounding point labeled
b. Insert the wire labeled
c. Insert the wire labeled
d. Insert the wire labeled
WARNING:
To protect power supplies from input voltage that might be
caused by miswired PDMs, before reinstalling the metal cover to the wiring
compartment apply AC voltage to the PDM (with disengaged PSM) to
make sure that two LEDs on the PDM are lit green and that the AC voltage
between AC terminal blocks A1-B1, B1-C1, C1-A1, A2-B2, B2-C2, and C2-A2
for three-phase delta PDM is not more than 264VAC when measured with
a digital voltage meter (DVM). Then turn off the AC breaker, de-energizing
the PDM, and install the metal cover and engage all AC PSMs.
NOTE:
The color of each AC power wire might vary.
Connect Power to a Three-Phase Delta AC Power Distribution Module
L1
into the input terminal labeled
into the input terminal labeled
L2
L3
into the input terminal labeled
.
GND
A2
.
.
B2
C2
.