CHAPTER 11 - START-UP PROCEDURES

11.3.4 Verify Flame Pattern and Combustion

1. Check the flame pattern through the observation
port of the heat exchanger. The flame should be
blue and stable. The flame should be over the length
of the burner head. It is not possible to determine
correct combustion by inspecting the colour and
pattern of the flame. It is important to measure
combustion with a calibrated flue gas analyser.
NOTICE
Combustion testing and adjustments must
be performed by a qualified installer, service
agency or the gas supplier. All combustion
measurements must be performed with
recently calibrated equipment (1 year max.) to
ensure proper reading and accuracy.
2. Test for CO2 or O2 and for CO during high firing rate.
The combustion readings must be within the range
listed in Table 6 on page 74. The CO level must not
exceed 150 ppm for natural gas or 200 ppm for
propane gas. Perform the following procedure to
manually place the burner into high fire.
a. Touch simultaneously on the
keys for 3 seconds to access the functions for the
installer. Reference Section 9.1 on page 51.
b. Enter the installer access code "054" by using
the
and
soft keys to select a digit location
and the
and
Touch the
soft key to enter the access code.
c. Touch the
soft key to highlight the Manual
Operation icon
d. Touch the
soft key while the FAN icon is
highlighted to manually fire the burner and
power the CH circulator(s).
Manual Operation
FAN
CH1
DHW
CH2
and
soft
soft keys to change the digit.
then touch the
soft key.
Released
O
O
O
NOTICE
An adequate CH load must be present to dissipate
the heat generated during the combustion test. If an
adequate CH load is not available, an indirect water
heater can be used to dissipate the heat by creating
a DHW call which will enable the DHW circulator.
e. Touch the
soft key to adjust the firing rate
from 1% to 100%. Hold down the
rapidly increase the firing rate.
f.
Touch the
soft key while the FAN icon is
highlighted to shutdown the burner.
3. If the combustion levels during high fire (100%) are
outside the acceptable levels, adjust the THROTTLE
SCREW (see Fig. 35 on page 73) according to
Table 6 on page 74.
4. Once the combustion level is set at high fire (100%),
manually place the boiler into low fire (1%) mode by
touching the
soft key to adjust firing rate down.
5. Verify the combustion levels during low fire (1%) are
within the acceptable combustion levels in Table 6
on page 74.
WARNING
If the combustion levels at low fire (1%) are
not within the range given in Table 6 on page
74, shut the boiler down and contact Ideal
Technical Support. Failure to comply with
this requirement can result in substantial
property damage, serious injury, or death.
Table 5 - Throttle Screw Adjustment
Direction
Clockwise
Counter-Clockwise

Fig. 35 - Throttle Screw Location

Throttle Screw
soft key to
EXALT Solo/Combi
Decrease CO 2
Increase O 2
Increase CO 2
Decrease O 2
73