Removal Of An Existing Boiler From A Common Vent System - IDEAL EXALT Solo 110 Installation & Maintenance Manual

Hide thumbs Also See for EXALT Solo 110:
Table of Contents

Advertisement

CHAPTER 2 - COMBUSTION AIR & VENTING
BEST PRACTICE
BEST PRACTICE
In order to reduce the potential risks associated
with indoor contaminates (see list in Section
2.1 on page 5), flammable vapors and tight
housing construction with little or no infiltration
air, it is recommended to pipe uncontaminated
combustion air directly from the outdoors to the
appliance. This practice also promotes higher
system efficiency by reducing heated indoor
air from being exhausted from the house and
replaced by cold infiltration air into the house.
DANGER
Verify installed combustion air and vent piping
are sealed gas tight and meet all provided instruc-
tions and applicable codes, failure to comply will
result in serious injury, or death.
WARNING
Failure to properly support the vent system can
cause the venting system to fail, resulting in
substantial property damage, serious injury, or
death.
NOTICE
Install combustion air and vent pipe as detailed
in the EXALT Vent Supplement included in the
boiler installation envelope. Refer to optional
vent kit instructions for additional vent
installation instructions.
2.6.
Removal of an Existing Boiler from a
Common Vent System
BEST PRACTICE
BEST PRACTICE
When an existing boiler is removed from a common
venting system, the common venting system
is likely to be too large for proper venting of the
remaining appliances. At the time of removal of an
existing boiler, the following steps shall be followed
with each appliance remaining connected to the
common venting system placed in operation, while
the other appliances remaining connected to the
common venting system are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
3. Insofar as is practical:
Close all exterior building doors and windows
and all doors between the space in which the
appliances remaining connected to the com-
mon venting system are located and other
spaces of the building.
Turn on clothes dryers and any appliance not
connected to the common venting system.
Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they will operate at
maximum speed.
Do not operate a summer exhaust fan.
Close fireplace dampers.
4. Place in operation the appliance being inspected.
Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a ciga-
rette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting sys-
tem properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers, and any other gas-burning appliance to
their previous condition of use.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code (NFPA 54
/ ANSI Z223.1) for installations in the U.S. or CAN/CSA
B149.1 for installations in Canada. When resizing any
portion of the common venting system, the common
venting system should be resized to approach the
minimum size as determined using the appropriate
tables in Chapter 13 of the National Fuel Gas Code
(NFPA 54 / ANSI Z223.1) for installations in the U.S. or
CAN/CSA B149.1 for installations in Canada.
DANGER
Do not install the EXALT into a common vent with
any other gas or oil appliances. This will cause flue
gas spillage or appliance malfunction, resulting
in substantial property damage, serious injury, or
death.
9

Advertisement

Table of Contents
loading

Table of Contents