Fig. 24 - Condensate Drain Assembly - IDEAL EXALT Solo 110 Installation & Maintenance Manual

Hide thumbs Also See for EXALT Solo 110:
Table of Contents

Advertisement

CHAPTER 6 - INSTALLING VENT/COMBUSTION AIR & CONDENSATE DRAIN
8. Route the tube from the condensate drain assem-
bly to a floor drain or condensate pump.
NOTICE
When selecting and installing a condensate pump,
ensure the pump is approved for use with condens-
ing appliances. The pump should be equipped with
an overflow switch to prevent property damage
from potential condensate spillage.
9.
The EXALT will typically produce a condensate that
is considered slightly acidic with a pH content be-
low 4.0. Install a neutralizing filter if required by au-
thority having jurisdiction.
RETAINING NUT
RETENTION
CLIP
(FOR SOLO
MODELS ONLY
PLASTIC BALL
(NOT SHOWN)
CONDENSATE
DRAIN ASSEMBLY
38
The condensate drain assembly must remain
filled with water. Extended periods of non use or
high temperature operation may allow the water
to evaporate. Periodically check the water level in
the condensate drain assembly and fill with water
as necessary. Failure to keep the condensate drain
assembly full of water can result in substantial
property damage, serious injury, or death.
The
and allow unrestricted flow of condensate. The
condensate should not be subject to conditions
where freezing could occur. If the condensate is
subjected to freezing or becomes obstructed , it can
leak, resulting in potential water damage to the
boiler and surrounding area.
SEALS
FILL PLUG WITH VACCUM
BREAK PORT
COMPRESSION NUT
WITH RUBBER SEAL
Flexible tubing
(or 3/4 PVC/
CPVC Piping to
Drain)

Fig. 24 - Condensate Drain Assembly

WARNING
CAUTION
drain assembly must remain unobstructed
RETENTION
CLIP
(FOR SOLO
MODELS ONLY