• Four mounting screws, compatible with the rack design, 
must be used and hand‐tightened to ensure secure 
installation. Choose a mounting location where all four 
mounting holes line up with those of the mounting bars of 
the 19‐inch rack mount cabinet. 
• A suitably rated and approved branch circuit breaker shall 
be provided as part of the building installation. Follow local 
code when purchasing materials or components. 
• Consideration must be given to the connection of the 
equipment to the supply circuit. Appropriate consideration 
of equipment nameplate ratings must be used when 
addressing this concern. Do not overload the circuit. 
• Reliable grounding of rack‐mounted equipment must be 
maintained. Particular attention must be given to power 
supply connections other than direct connections to the 
branch circuits, such as power strips. 
• As shipped from the factory this SonicWall product includes 
two power supplies for redundant AC power and added 
reliability. A field conversion is available to convert to DC 
mains. 
• To disconnect AC power, both power cords must be 
removed.
• The included power cord(s) are approved for use only in 
specific countries or regions. Before using a power cord, 
verify that it is rated and approved for use in your location. 
• This model is shipped as AC mains configuration using 
standard 3 conductor appliance couplers. A field 
conversion is available to change to DC mains. The DC 
mains connector uses terminal posts with the polarity 
marked.
• To disconnect DC power, an external properly‐related 
disconnect device must be provided by building or rack 
installation.
• Do not connect AC configured products to DC mains, and 
do not connect DC configured products to AC. Detailed 
instructions are provided with the DC conversion kit. 
Product must be configured as all DC or all AC. 
• DC rating includes tolerances. Do not operate product 
outside of range shown on product label. 
• DC configuration includes input cable with protective 
earthing conductor (Green and Yellow wire). This 
conductor is required to be connected to safety earth 
ground of circuit. 
• Thumbscrews should be tightened with a tool after both 
installation and subsequent access to the rear of the 
product. 
SonicWall SuperMassive 9200/9400/9600 Getting Started Guide