System modifications during redundant operation

10.5 Editing CPU parameters

10.5
Editing CPU parameters
10.5.1
Editing CPU parameters
Only certain CPU parameters (object properties) can be edited in operation. These are
highlighted in the screen forms by blue text. If you have set blue as the color for dialog box
text on the Windows Control Panel, the editable parameters are indicated in black
characters.
Note
If you edit any protected parameters, the system will reject any attempt to changeover to the
CPU containing those modified parameters. The event W#16#5966 is written to the
diagnostic buffer. and you will then have to restore the wrongly changed parameters in the
parameter configuration to their last valid values.
Table 10- 1
Modifiable CPU parameters
Tab
Startup
Cycle/clock memory
Memory
Time-of-day interrupts (for each time-of-
day interrupt OB)
Watchdog interrupt (for each watchdog
interrupt OB)
Diagnostics/clock
Security
H parameter
The selected new values should match both the currently loaded and the planned new user
program.
174
Editable parameter
Monitoring time for signaling readiness by modules
Monitoring time for transferring parameters to modules
Cycle load due to communication
Local data for the individual priority classes
"Active" checkbox
"Execution" list box
Starting date
Time
Execution
Phase offset
Correction factor
Security level and password
Test cycle time
Maximum cycle time extension
Maximum communication delay
Maximum inhibit time for priority classes > 15
Minimum I/O retention time
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB