Synchronization modules
12.2 Installation of fiber-optic cables
Cable pull-in
Note the points below when pulling-in fiber-optic cables:
● Always observe the information on pull forces in the data sheet of the corresponding
fiber-optic cable.
● Do not reel off any greater lengths when you pull in the cables.
● Install the fiber-optic cable directly from the cable drum wherever possible.
● Do not spool the fiber-optic cable sideways off the drum flange (risk of twisting).
● You should use a cable pulling sleeve to pull in the fiber-optic cable.
● Always observe the specified bending radii.
● Do not use any grease or oil-based lubricants.
You may use the lubricants listed below to support the pulling-in of fiber-optic cables.
– Yellow compound (Wire-Pulling, lubricant from Klein Tools; 51000)
– Soft soap
– Dishwashing liquid
– Talcum powder
– Detergent
Pressure
Do not exert any pressure on the cable, for example, by the inappropriate use of clamps
(cable quick-mount) or cable ties. Your installation should also prevent anyone from stepping
onto the cable.
Influence of heat
Fiber-optic cables are highly sensitive to direct heat, which means the cables must not be
worked on using hot-air guns or gas burners as used in heat-shrink tubing technology.