Resetting The Cpu410-5H To Factory Settings; Table 9- 2 Cpu Properties In The Factory Settings - Siemens SIMATIC PCS 7 CPU 410-5H System Manual

Process control system / process automation
Table of Contents

Advertisement

9.3

Resetting the CPU410-5H to factory settings

CPU factory settings
A general memory reset is performed when you reset the CPU to its factory settings and the
properties of the CPU are set to the following values:
Table 9- 2
Properties
Contents of the diagnostics buffer
IP parameters
SNMP parameters
Operating hours counter
Date and time
Procedure
Proceed as follows to reset a CPU to its factory settings:
1. Switch off the line voltage.
2. Switch on the line voltage while pressing and holding down the Reset button.
3. Wait until LED lamp image 1 from the subsequent overview is displayed. In this lamp
pattern, INTF flashes at 0.5 Hz. EXTF, BUSxF, MAINT, IFMxF, RUN, and STOP remain
unlit.
4. Wait until LED lamp image 2 from the subsequent overview is displayed. In this LED
pattern, INTF is lit. EXTF, BUSxF, MAINT, IFMxF, RUN, and STOP remain unlit.
5. The CPU performs a memory reset and the STOP LED flashes at 2 Hz.
The CPU is now reset to its factory settings. It starts up and switches to STOP operating
state or links up. The event "Reset to factory setting" is entered in the diagnostics buffer.
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
CPU properties in the factory settings
Special functions of the CPU 410-5H
9.3 Resetting the CPU410-5H to factory settings
Value
Empty
None
Default values
0 without battery backup
01.01.94, 00:00:00 without battery backup
141