Siemens SIMATIC PCS 7 CPU 410-5H System Manual page 222

Process control system / process automation
Table of Contents

Advertisement

Technical data
14.1 Technical specifications of the CPU 410-5H; (6ES7 410-5HX08-0AB0)
Time synchronization
Supported
On DP, master
On DP, slave
On the AS, master
On the AS, slave
On Ethernet using NTP
Time difference in the system with synchronization via
Ethernet, max.
Interfaces
Number of RS 485 interfaces
Number of other interfaces
PROFINET IO
Number of PROFINET interfaces
1. Interface
Interface type
Physics
Electrically isolated
Power supply at interface (15 to 30 V DC), max.
Number of connection resources
Functionality
DP master
DP slave
DP master
Number of connections, max.
Transmission rate, max.
Number of DP slaves, max.
Number of slots per interface, max.
Services
PG/OP communication
Routing
Global data communication
S7 basic communication
S7 communication
S7 communication, as client
S7 communication, as server
Support for constant bus cycle time
Isochronous mode
SYNC/FREEZE
Activation/deactivation of DP slaves
222
6ES7410-5HX08-0AB0
Yes
Yes
Yes
Yes
Yes
Yes; as client
10 ms
1; PROFIBUS DP
2; 2x synchronization
2
integrated
RS 485/PROFIBUS
Yes
150 mA
16
Yes
No
16
12 Mbps
96
1632
Yes
Yes
No
No
Yes
Yes
Yes
No
No
No
No
System Manual, 09/2014, A5E31622160-AB
CPU 410-5H Process Automation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents